2015-06-25 11:10:09RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC-RESIDENTIAL
  
 1- TU PLUS ROOF TILE UNDERLAYMENT FL5259-R22:
 SELF-ADHERING UNDERLAYMENTS NEED TO COMPLY WITH THE
 DESIGN PRESSURES OF ALL ROOF ZONES. MAXIMUM DESIGN
 PRESSURE FOR SELECTED UNDERLAYMENT 5.6.4.1 IS -90 PSF.
 THIS PRESSURE DOESN'T MEET THE CORNERS DESIGN
 PRESSURES.THIS BUILDING IS LOCATED IN EXPOSURE "C" AND
 THE DESIGN PRESSURE FOR CORNER AREAS IS -95.12 PSF.
 PLEASE SELECT ANOTHER ASSEMBLY THAT MEETS THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, INCLUDING THE CORNER
 AREAS. SEC. R301 OF 2010 FBC-RESIDENTIAL.
  