Plan Review Notes For Permit 15060951 |
Permit Number |
15060951 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-07-08 16:45:19 | FAILED 2ND ELECTRICAL REVIEW AS NOTED BELOW: | | I DON'T KNOW IF THE RE-SUBMITTAL IS FOR THE SAME | | LOCATION AS THE ORIGINAL PERMIT. THE ORIGINAL RISER | | DIAGRAM WAS FEEDING A 150 AMP PANEL AND THE RESUB IS | | FOR A 125 AMP PANEL. | | IN ADDITION TO THIS, THE COMMENTS PREVIOUSLY MENTIONED | | WERE NOT ALL ADDRESSED. YOU MUST REVISE YOUR SUBMITTAL | | TO ADDRESS THE COMMENTS HEREIN STATED. | | THE SITE PLAN PROVIDED DOES NOT CLEARLY INDICATE THE | | LOCATION OF THE METER. AS IS IT APPEARS TO BE BEHIND | | THE POOL EQUIPMENT PAD, IN VIOLATION OF NEC 110.26. | | | | IF YOU HAVE ANY QUESTION, PLEASE DO NOT HESITATE TO | | CONTACT ME AT (561) 805-6746 | | MIKE ALBARRAN ELECTRICAL PLANS EXAMINER |
|