Plan Review Notes
Plan Review Notes For Permit 15060949
Permit Number 15060949
Review Stop B
Sequence Number 2
Notes
Date Text
2015-07-08 09:19:14RESIDENTIAL (R3) ROOF OVER, SECOND BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC-RESIDENTIAL
  
 1- TAMKO NOA 12-0716.09 SUBMITTED FOR RECOVERY DECK
 REQUIRES FASTENERS WITHDRAWAL RESISTANCE TEST (TAS
 105). SEE NOTE IN BOLD IN PAGE 17 OF 19 OF NOA
 SUBMITTED. PROVIDE 2 COPIES OF THE TAS 105 TEST.
 REQUIRED TO VERIFY THE CALCULATED DESIGN PRESSURES
 REQUIRED BY SEC. R301 OF 2010 FBC-RESIDENTIAL.
 THEN, ENGINEER TO REVISE THE RAS 117 CALCULATIONS BASED
 ON THE TAS 105 RESULTS.
  