Plan Review Notes For Permit 15060949 |
Permit Number |
15060949 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-07-08 09:19:14 | RESIDENTIAL (R3) ROOF OVER, SECOND BUILDING REVIEW | | COMMENTS. | | CODE: 2010 FBC-RESIDENTIAL | | | | 1- TAMKO NOA 12-0716.09 SUBMITTED FOR RECOVERY DECK | | REQUIRES FASTENERS WITHDRAWAL RESISTANCE TEST (TAS | | 105). SEE NOTE IN BOLD IN PAGE 17 OF 19 OF NOA | | SUBMITTED. PROVIDE 2 COPIES OF THE TAS 105 TEST. | | REQUIRED TO VERIFY THE CALCULATED DESIGN PRESSURES | | REQUIRED BY SEC. R301 OF 2010 FBC-RESIDENTIAL. | | THEN, ENGINEER TO REVISE THE RAS 117 CALCULATIONS BASED | | ON THE TAS 105 RESULTS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|