Plan Review Notes For Permit 15060949 |
Permit Number |
15060949 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-06-23 08:09:15 | RESIDENTIAL (R3) ROOFING, BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC-RESIDENTIAL | | | | | | 1- PERMIT APPLICATION STATES "COVER OVER ROOF". IF THIS | | IS A RECOVER APPLICATION, THEN NEED TO PROVIDE PRODUCT | | APPROVAL FOR SUCH INSTALLATION. PRODUCT APPROVAL NOA | | 13-1022.15 SUBMITTED IS NOT FOR THAT APPLICATION. | | CLEARLY IDENTIFY SELECTED ASSEMBLY. AND, PROVIDE SIGNED | | AND SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY | | ALLOWS NAIL ENHANCING. CALCULATIONS ARE REQUIRED TO | | MEET THE DESIGN PRESSURES OF SEC. R301.1 OF 2010 | | FBC-RESIDENTIAL. DCA RULE 9N-3. | | | | 2- SELECTED ASSEMBLY FROM NOA 13-1022.15 IS FOR AN | | INSULATED ASSEMBLY. SPECIFY INSULATION TO BE USED. SEC. | | 107.2.1 CITY AMENDMENTS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|