2015-08-21 11:18:49RESIDENTIAL (R3) MECHANICAL REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- EQUIPMENT SIZING CALCULATIONS SUBMITTED ARE DONE FOR
 THE WRONG LOCATION. THIS IS CITY OF WEST PALM BEACH NOT
 FORT LAUDERDALE. ENGINEER DOING THE CALCULATIONS TO
 REVISE AS REQUIRED. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 2- ENERGY CALCULATIONS SUBMITTED NEED TO HAVE THE
 OWNER/AGENT SIGNATURE AS REQUIRED BY SEC. 103.2.3.2 OF
 2010 FBC-ENERGY CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712