2015-08-20 17:26:29 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY ELECTRICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) NEC 250.52 & 210.70 - PROVIDE AN ELECTRICAL FLOOR | | PLAN SHOWING THE LOCATION OF ALL REQUIRED LIGHTING AND | | RECEPTACLE OUTLETS AND SHOW CIRCUITS. | | | | 2) NEC 220.40 - SUBMIT ELECTRICAL LOAD CALCULATIONS. | | | | 3) FBC 107.3.5.3 - SUBMIT PANEL SCHEDULES. | | | | 4) NEC 240.24(A) & (B) PANELS SHALL BE READILY | | ACCESSIBLE AND EACH OCCUPANT SHALL HAVE READY ACCESS. | | SPECIFY THE LOCATIONS OF THE PANELS ON THE ELECTRICAL | | FLOOR PLAN. | | | | 5) FBC- 107.3.5.3 - PROVIDE AN ELECTRIC SERVICE RISER | | WITH WIRE SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. | | | | 6) NEC 110.9 - SPECIFY THE A.I.C. RATING OF THE | | ELECTRICAL EQUIPMENT ON THE PLANS. | | | | 7) NEC 210.70 (A) (2) - PROVIDE AT LEAST ONE WALL | | SWITCH CONTROLLED LIGHTING OUTLET TO PROVIDE | | ILLUMINATION ON THE EXTERIOR SIDE OF OUTDOOR ENTRANCES | | OR EXISTS WITH GRADE LEVEL ACCESS. | | |
|