Plan Review Notes
Plan Review Notes For Permit 15060911
Permit Number 15060911
Review Stop M
Sequence Number 1
Notes
Date Text
2015-07-07 11:26:581ST REVIEW: FBC 2010 MECHANICAL
  
 1) ENERGY COMPLIANCE FORM 506-2010: A) THE CONSTRUCTION
 MATERIALS LISTED FOR THE LOADING DOCK WALLS IN THE
 INPUT DATA REPORT SHOW SOLID WALLS WHICH DOES NOT MATCH
 THE PLAN WHICH SHOWS SEVEN INSULATED ROLL-UP DOORS. B)
 THE REPORT IS LISTING ONLY TWO MAN DOORS HOWEVER THERE
 ARE THREE SHOWN ON THE PLAN.
 2) THE AIR SYSTEM SIZING SUMMARIES INDICATE THE
 LOCATION OF THE PROJECT TO BE IN MIAMI. PLEASE REVISE
 THE CALCS TO INDICATE WEST PALM BEACH LOCATION, AND USE
 THE CORRECT DB/WB TEMPERATURES PER TABLE 1A MANUAL N.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  