2015-06-23 15:34:14 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) SHEET A 1 - THERE IS AN INCORRECT REFERNECE TO THE |
| FIRE CODE. |
| THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| APPLICABLE CODES OR STANDARDS. |
| |
| 2) SHEET A 5 - THE NEW EXIT DOORS SHALL SWING IN THE |
| DIRECTION OF EGRESS. PLEASE REVIEW THE FOLLOWING: |
| NFPA 101 CHAPTER 7, MEANS OF EGRESS |
| 7.2.1.4.3 DOOR LEAF ENCROACHMENT |
| 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE |
| REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, |
| OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT |
| MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A |
| CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, |
| UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: |
| (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| EXISTING BUILDING. |
| (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS |
| PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED |
| WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY |
| OPEN. |
| |
| 3) NO EXIT DOOR SHALL BE LOCKED FROM THE EGRESS SIDE. |
| ANY AND ALL LOCKING MECHANISMS SHALL BE COMPLAINT WITH |
| CHAPTER 7 OF THE FLORIDA FIRE PREVENTION CODE. PROVIDE |
| A DOOR SCHEDULE INCLUDING EXIT AND LATCH HARDWARE. |
| |
| 4) SHEET E 2.01 - PROVIDE AND EXIT SIGN AT THE SIDE |
| EXIT DOOR. |
| |
| |