Plan Review Notes For Permit 15060911 |
Permit Number |
15060911 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-07-23 11:18:39 | APPROVED W/PROVISO: THERE ARE A COUPLE OF ITEMS WHICH | | ARE MISSING FROM THE DRAWINGS THAT HAVE BEEN MARKED AND | | MENTIONED ON THE APPROVED PLANS. WHICH SHALL BE | | ADDRESSED FOR INSPECTION. | | 1. NEC 600.5(A) REQUIRED BRANCH CIRCUIT. EACH | | COMMERCIAL BUILDING AND EACH COMMERCIAL OCCUPANCY | | ACCESSIBLE TO PEDESTRIANS SHALL BE PROVIDED WITH AT | | LEAST ONE OUTLET IN AN ACCESSIBLE LOCATION AT EACH | | ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE | | LIGHTING SYSTEM USE. THE OUTLET(S) SHALL BE SUPPLIED BY | | A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES THAT | | SUPPLIES NO OTHER LOAD. SERVICE HALLWAYS OR CORRIDORS | | SHALL NOT BE CONSIDERED ACCESSIBLE TO PEDESTRIANS. | | 2. FBC-B 1006.3 EXITS SHALL BE MARKED BY AN APPROVED | | SIGN READILY VISIBLE FROM ANY DIRECTION OF EXIT ACCESS. | | EVERY EXIT SHALL BE SUITABLY ILLUMINATED BY A RELIABLE | | LIGHT SOURCE. EXTERNALLY & INTERNALLY ILLUMINATED SIGNS | | SHALL BE VISIBLE IN BOTH NORMAL & EMERGENCY LIGHTING. |
|