Plan Review Notes For Permit 15060911 |
Permit Number |
15060911 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-06-28 06:42:41 | BUILDING PLAN REVIEW | | PERMIT: 15060911 | | ADD: 1220 ORTEGA RD | | CONT: WILBUR HOBGOOD CONST. | | TEL: (561)691-9686 | | 2010 FLORIDA BUILDING CODE W | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | SYSTEMS, | | AND SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | FLORIDA BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | DATE: SUN. JUNE 28/ 2015 | | ACTION: BUILDING PROVISO | | | | A SEPARATE ROOFING PERMIT & REVIEW REQUIRED. | | ROOFING PRODUCT APPROVAL : 13-0529.14 | | JOHN MANVILLE MODIFIED BITUMEN OVER WOOD DECK | | NO SUB-SYSTEM WAS IDENTIFIED, WILL NEED TO SELECT A | | SUB-SYSTEM BETWEEN | | PAGES 10-26. NOTE PRESSURES ARE GOOD FOR ZONE # 1 BUT | | WILL REQUIRE | | ENHANCED FASTENING IN ZONES 2 & 3. SEE IF LIMITATION 7 | | OR 9 APPLIES. | | | | PAGE 27 LIMITATION # 7 REQUIRES RAS 117 CALCULATIONS TO | | BE COMPLETED BY | | EITHER AN ARCHITECT OR ENGINEER REGISTERED WITH THE | | STATE OF FLORIDA. | | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | |
|