2015-06-27 16:00:50 | TRAVELLING WITH PERMIT #15060642 |
2015-06-27 15:14:46 | 6/27/2015 |
| PROJECT: 3916 GREEWOOD RENNOVATION |
| PERMIT#: 14020194 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW REVISION #15060882 |
| ACTION: DENIED |
| |
| PERMIT# 14020194 INSPECTION RESULTS DATED 03/03/2014 |
| NOTE FROM DOUG HARVEY: |
| STOP WORK ORDER ISSUED. WORK BEING DONE |
| IN ALL TRADES. PLANS AND COMPLETE |
| PERMITS NEEDED. NO WORK AND NO POWER |
| UNTIL FULL PERMIT IS ISSUED AND |
| COMPLETED. ELECTRICAL NOT READY. NO |
| WIRES AT SERVICE. |
| |
| PERMIT #14020194 IS NOT CURRENTLY EXPIRED. AS A RESULT |
| A NEW PERMIT APPLICATION IS NOT REQUIRED. THE SCOPE OF |
| WORK HAS CHANGED. THE PERMIT APPLICATION IS CHANGED TO |
| REVISION #15060882. |
| |
| 1) INDICATE WHERE THE SMOKE DETECTORS ARE INSTALLED. |
| WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL |
| 314 AND 315. |
| |
| 2) NEC 210.12, 406.11 |
| ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 |
| |
| 3) NEC 210.52(C)(3) BATHROOM BRANCH CIRCUITS. IN |
| ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY |
| OTHER PARTS OF THIS SECTION, AT LEAST ONE 20-AMPERE |
| BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM |
| RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER |
| OUTLETS. |
| 3A) NEC 210.52 (D) BATHROOMS. IN DWELLING UNITS, AT |
| LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN |
| BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH |
| BASIN. THE RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL |
| OR PARTITION THAT IS ADJACENT TO THE BASIN OR BASIN |
| COUNTERTOP, OR INSTALLED ON THE SIDE OR FACE OF THE |
| BASIN CABINET NOT MORE THAN (12 IN.) BELOW THE |
| COUNTERTOP. |
| |
| 4) NEC 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER |
| PROTECTION FOR PERSONNEL |
| (A) DWELLING UNITS. ALL 125-VOLT, SINGLE-PHASE, 15- AND |
| 20-AMPERE RECEPTACLES INSTALLED IN THE LOCATIONS |
| SPECIFIED IN (1) THROUGH (8) SHALL HAVE GROUND-FAULT |
| CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. |
| (1) BATHROOMS |
| |
| 5) WPB AMENDEMNTS TO THE FBC 107.3.5.3 |
| PROVIDE A PANEL SCHEDULE AND LOAD CALCULATION. EVERY |
| CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY |
| IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC |
| PURPOSE OR USE. NEC 408.4 |
| |
| 6) NEC 110.9 |
| VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS HAS A |
| FAULT CURRENT RATING THAT IS SUFFICIENT AT NOMINAL |
| CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| INTERRUPTED. |
| |
| 7) FBC-EXISTING 708.3 RESIDENTIAL OCCUPANCIES. |
| IN GROUP R-2, R-3, AND R-4 OCCUPANCIES AND BUILDINGS |
| REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL, |
| THE REQUIREMENTS OF SECTIONS 708.3.1 THROUGH 708.3.7 |
| SHALL BE APPLICABLE ONLY TO WORK AREAS LOCATED WITHIN A |
| DWELLING UNIT. INDICATE WHAT IS EXISTING TO REMAIN AND |
| WHAT IS PROPOSED TO BE NEW. IT IS NOT CLEAR FROM WHAT |
| IS SUBMITTED WHAT IS EXISTING AND WHAT IS PROPOSED. |
| |
| 8) WPB AMENDMENTS TO FBC 107.3.1 |
| TWO COPIES OF ALL PLANS AND SPECIFICATIONS ARE REQUIRED |
| FOR SUBMITTAL WITH AN APPLICATION FOR PERMIT. ONCE |
| REVIEWED AND READY FOR ISSUANCE, ONE SET TO BE RETAINED |
| BY THE BUILDING OFFICIAL FOR THE PURPOSE OF RECORD |
| KEEPING AND THE OTHER TO BE RETURNED TO THE APPLICANT |
| UPON ISSUANCE OF THE PERMIT. |
| |
| 9) WPB AMENDMENTS TO FBC 107.2.1 |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. |
| |
| 10) WPB AMENDMENTS TO FBC 107.2.1.4 |
| QUALITY OF BUILDING PLANS. BUILDING PLANS SHALL BE |
| DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL |
| PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |
| |