Plan Review Notes For Permit 15060809 |
Permit Number |
15060809 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-06-20 02:43:48 | 1) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | SPECIFICATIONS FOR REVIEW. ALL EQUIPMENT SHALL BE | | LISTED AND LABELED PER THE 2010 FBC-RESIDENTIAL, SEC. | | G2404.3, WPB AMEND. TO 2010 FBC SEC. 107.1. | | 2) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES | | THAT ARE USED FOR THE SIZING OF THE GAS LINE. 2010 | | FBC-RESIDENTIAL, SEC. G2413.3. | | 3) ONE COPY OF THE PLANS IS DONE IN PENCIL. PLANS IN | | PENCIL ARE UNACCEPTABLE. | | 4) INDICATE THE PSI OF THE SYSTEM. IF IT IS A HYBRID | | PRESSURE SYSTEM, SHOW WHERE THE PRESSURE REGULATOR IS | | LOCATED ON THE PLAN. WPB AMEND. TO 2010 FBC SEC. | | 107.2.1. | | 5) SUBMIT A DETAIL OF THE VENT FOR THE APPLIANCE. SHOW | | THE SIZE OF THE VENT. THE VENT TERMINATION LOCATION | | SHALL BE INSTALLED PER THE MANUFACTURER'S INSTALLATION | | INSTRUCTIONS IF THIS IS A DDIRECT VENT APPLIANCE. | | 6) IF YOU ARE ALSO DOING THE WATER PIPING SUBMIT A | | WATER RISER FOR THE COLD & HOT WATER LINES AND SHOW THE | | TYPE OF PIPE & SIZES AND THE SOURCE OF THE WATER | | SUPPLY. INCLUDE THIS UNDER THE DESCRIPTION OF WORK ON | | THE APPLICATION.WPB AMEND. TO 2010 FBC SEC. 107.3.5.3. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|