2015-06-19 12:16:44 | 1) SUBMIT TWO COPIES OF THE MANUF. SPECIFICATIONS FOR | | THE GAS POOL HEATER. THE HEATER SHALL BE LISTED AND | | LABELED PER FBC-RESIDENTIAL, SEC. G2404.3. | | 2) THE POOL HEATER SHALL COMPLY WITH THE FBC-ENERGY | | SEC. 403.9.1.1 -ALL GAS- AND OIL-FIRED POOL AND SPA | | HEATERS SHALL HAVE A MINIMUM THERMAL EFFICIENCY OF 78 | | PERCENT FOR HEATERS MANUFACTURED BEFORE APRIL 16, 2013 | | AND NOT LESS THAN 82 PERCENT FOR HEATERS MANUFACTURED | | ON OR AFTER APRIL 16, 2013 WHEN TESTED IN ACCORDANCE | | WITH ANSI Z 21.56. POOL HEATERS FIRED BY NATURAL GAS OR | | LPG SHALL NOT HAVE CONTINUOUSLY BURNING PILOT LIGHTS. | | 3) THE COPY OF THE SURVEY SUBMITTED FOR THE GAS SHOWS A | | NEW POOL HEATER BUT THERE IS NO POOL SHOWN ON THE | | SURVEY. CLARIFY. | | 4) SUBMIT TWO COPIES OF THE GAS SIZING TABLES THAT DO | | NOT HAVE THE VILLAGE OF WELLINGTON STAMP ONIT OR THEIR | | PERMIT NUMBER.WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | 5) INCLUDE THE TOTAL BTU LOAD OF THE EXISTING GAS LINE | | THAT IS BEING CONNECTED. WPB AMEND. TO 2010 FBC SEC. | | 107.2.1. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|