Plan Review Notes
Plan Review Notes For Permit 15060748
Permit Number 15060748
Review Stop G
Sequence Number 1
Notes
Date Text
2015-06-19 12:16:441) SUBMIT TWO COPIES OF THE MANUF. SPECIFICATIONS FOR
 THE GAS POOL HEATER. THE HEATER SHALL BE LISTED AND
 LABELED PER FBC-RESIDENTIAL, SEC. G2404.3.
 2) THE POOL HEATER SHALL COMPLY WITH THE FBC-ENERGY
 SEC. 403.9.1.1 -ALL GAS- AND OIL-FIRED POOL AND SPA
 HEATERS SHALL HAVE A MINIMUM THERMAL EFFICIENCY OF 78
 PERCENT FOR HEATERS MANUFACTURED BEFORE APRIL 16, 2013
 AND NOT LESS THAN 82 PERCENT FOR HEATERS MANUFACTURED
 ON OR AFTER APRIL 16, 2013 WHEN TESTED IN ACCORDANCE
 WITH ANSI Z 21.56. POOL HEATERS FIRED BY NATURAL GAS OR
 LPG SHALL NOT HAVE CONTINUOUSLY BURNING PILOT LIGHTS.
 3) THE COPY OF THE SURVEY SUBMITTED FOR THE GAS SHOWS A
 NEW POOL HEATER BUT THERE IS NO POOL SHOWN ON THE
 SURVEY. CLARIFY.
 4) SUBMIT TWO COPIES OF THE GAS SIZING TABLES THAT DO
 NOT HAVE THE VILLAGE OF WELLINGTON STAMP ONIT OR THEIR
 PERMIT NUMBER.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 5) INCLUDE THE TOTAL BTU LOAD OF THE EXISTING GAS LINE
 THAT IS BEING CONNECTED. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR