| PROJECT: PNC BANK SECURITY AND CCTV |
| PERMIT#: 15060747 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED. |
| |
| REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| COMMENTS: |
| |
| 1) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| THE PERSON RESPONSIBLE FOR THE DESIGN WPB AMENDMENTS TO |
| FBC SECTION 107.2.1 |
| 1A) THE SUBMITTED PLANS ARE PHOTOCOPIED PLANS OF AN |
| ORIGINAL SIGNED AND SEALED PLAN. PLANS, SPECIFICATIONS, |
| REPORTS OR OTHER DOCUMENTS PREPARED BY THE DESIGN |
| PROFESSIONAL AND BEING FILED FOR PUBLIC RECORD SHALL |
| HAVE THE SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL |
| AFFIXED TO THE DOCUMENT. |
| FL ADMIN CODE 61G15-23.002 ENGINEERS |
| |
| 2) PROVIDE TWO COPIES OF ALL PLANS AND SPECIFICATIONS |
| FOR SUBMITTAL WITH AN APPLICATION FOR PERMIT. ONE COPY |
| TO BE REATAINED FOR PUBLIC RECORD AND THE OTHER TO BE |
| RELEASED BACK TO THE CONTRACTOR FOR INSTALLATION AND |
| INSPECTION PURPOSES. WPB AMENDMENTS TO FBC SECTION |
| 107.3.1. |
| |
| 3) PROVIDE SUPPORTING DOCUMENTATION SUCH AS A CONTRACT |
| EQALLING THE STATED VALUE FOR THIS SCOPE OF WORK. FOR |
| PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS |
| SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT . WPB AMENDMENTS |
| TO FBC SECTION 109.3 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |