Plan Review Notes For Permit 15060742 |
Permit Number |
15060742 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-07-27 18:15:29 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. REVISE THE PLAN TO SHOW COMPLIANCE WITH FBC 2010 | | RESIDENTIAL 310, EXISTING BUILDING 704.1. | | | | FOR BEDROOM WINDOWS, NOTE EXISTING CONDITIONS (TYPE OF | | WINDOW) AND OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB | | 704.1. THE CLEAR OPENING CANNOT BE REDUCED BY MORE THAN | | 5%. | | | | TO PROVIDE FURTHER CLARIFICATION REGARDING INFORMATION | | NEEDED FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN | | HEIGHT: | | | | STATE WHAT TYPE OF WINDOW IS THERE NOW IN THE BEDROOMS | | - AWNING, CASEMENT, SINGLE HUNG? | | | | STATE WHAT THE EXISTING CLEAR OPENING DIMENSIONS ARE. | | CLEAR OPENING IS THE OPENING WHICH EXISTS WHEN THE | | WINDOW IS FULLY OPEN. | | | | STATE WHAT THE PROPOSED CLEAR OPENING DIMENSIONS ARE. | | THIS CAN BE OBTAINED FROM THE MANUFACTURER. | | | | | | |
|