Plan Review Notes
Plan Review Notes For Permit 15060725
Permit Number 15060725
Review Stop B
Sequence Number 2
Notes
Date Text
2015-09-03 14:49:12MALBARRAN'S DESK
2015-09-03 10:36:15BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060725
 ADD: 222 LAKEVIEW AVE.
 CONT: FASTRACK
 TEL: (561)304-7881
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 07/ 2015
 ACTION: BUILDING PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET A2.1 DETAIL J10 ELEVATION & A3.1 DETAIL E14
 THE HEADER OVER GARAGE DOOR OPENINGS NEEDS TO SHOW
 COMPLIANCE WITH 2010 FBC-B
 2104.1 MASONRY CONSTRUCTION. MASONRY CONSTRUCTION SHALL
 COMPLY WITH THE REQUIREMENTS OF SECTIONS 2104.1.1
 THROUGH 2104.4 AND WITH TMS 602/ACI 530.1/ASCE 6.
 ACI 530.1 SECTION 7.5.3.1 SHEAR REINFORCEMENT (STIRRUPS
 OR HAIRPINS) SHALL BE PROVIDED PARALLEL TO THE
 DIRECTION OF APPLIED SHEAR FORCE. SPACING OF THE SHEAR
 REINFORCEMENT SHALL NOT EXCEED THE LESSER OF D/2 OR 48
 INCHES. D- BOTTOM STEEL TO TOP OF BEAM.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  