Plan Review Notes For Permit 15060725 |
Permit Number |
15060725 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-06-25 12:42:45 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) PROVIDE A EXIT SIGN AT THE MANDOOR. | | | | 2) THE OVERHEAD DOOR PROVIDE A SPRINKLER HEAD | | OBSTRUCTION THAT SHALL BE CORRECTED. DUE TO THE REMODLE | | A FIRE SPRINKLER HEAD COVERAGE EVALUATION IS | | REQUIRED.PROVIDE A PROPOSED FIRE SPRINKLER PLAN. | | SEPARATE SHOP ARE REQUIRED FOR ANY FIRE SPRINKLER WORK. | | | | 3) A FIRE ALRM NOTIFICATION DEVICE IS REQUIRED INSIDE | | THE GARAGE. A FIRE ALARM NOTIFICATION REVIEW IS | | REQUIRED. PROVIDE A PROPOSED FIRE ALARM PLAN. SEPARATE | | SHOP ARE REQUIRED FOR ANY FIRE ALARM WORK. | | | | 4) PROVIDE A NOTE INDICATING THE ACTIVIATION AND | | DURATION OF THE VENTILATION FAN. | | |
|