Plan Review Notes
Plan Review Notes For Permit 15060725
Permit Number 15060725
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-06-25 12:42:45THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) PROVIDE A EXIT SIGN AT THE MANDOOR.
  
 2) THE OVERHEAD DOOR PROVIDE A SPRINKLER HEAD
 OBSTRUCTION THAT SHALL BE CORRECTED. DUE TO THE REMODLE
 A FIRE SPRINKLER HEAD COVERAGE EVALUATION IS
 REQUIRED.PROVIDE A PROPOSED FIRE SPRINKLER PLAN.
 SEPARATE SHOP ARE REQUIRED FOR ANY FIRE SPRINKLER WORK.
  
 3) A FIRE ALRM NOTIFICATION DEVICE IS REQUIRED INSIDE
 THE GARAGE. A FIRE ALARM NOTIFICATION REVIEW IS
 REQUIRED. PROVIDE A PROPOSED FIRE ALARM PLAN. SEPARATE
 SHOP ARE REQUIRED FOR ANY FIRE ALARM WORK.
  
 4) PROVIDE A NOTE INDICATING THE ACTIVIATION AND
 DURATION OF THE VENTILATION FAN.
  