Plan Review Notes
Plan Review Notes For Permit 15060717
Permit Number 15060717
Review Stop M
Sequence Number 3
Notes
Date Text
2015-09-03 08:15:122ND REVIEW: FBC 2010 MECHANICAL
 PERMIT #15060717
 9/3/15
  
 1) PAGE 20 OF THE SUBMITTED TIE-DOWN ENGINEERING FROM
 STRUCTURAL EDGE ENGINEERING SHOWS MULTIPLE OPTIONS FOR
 ATTACHING THE RTU TO THE CURB. A SITE SPECIFIC DETAIL
 IS REQUIRED- OPTIONS ARE NOT ACCEPTABLE TO THE WPB
 BUILDING DEPARTMENT. PLEASE NOTE THAT WELDING THE UNIT
 TO THE CURB MUST BE IN COMPLIANCE WITH THE
 MANUFACTURER'S INSTALLATION RECOMMENDATIONS. PLEASE
 PROVIDE EVIDENCE THAT THIS IS AN ACCEPTABLE METHOD BY
 THE MANUFACTURER- OTHERWISE THE PRODUCT WARRANTY MAY BE
 VOIDED.
 2) SUBMIT PRODUCT DATA (CUT) SHEETS FOR THE RTU CURB