Plan Review Notes For Permit 15060717 |
Permit Number |
15060717 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2015-09-03 08:15:12 | 2ND REVIEW: FBC 2010 MECHANICAL | | PERMIT #15060717 | | 9/3/15 | | | | 1) PAGE 20 OF THE SUBMITTED TIE-DOWN ENGINEERING FROM | | STRUCTURAL EDGE ENGINEERING SHOWS MULTIPLE OPTIONS FOR | | ATTACHING THE RTU TO THE CURB. A SITE SPECIFIC DETAIL | | IS REQUIRED- OPTIONS ARE NOT ACCEPTABLE TO THE WPB | | BUILDING DEPARTMENT. PLEASE NOTE THAT WELDING THE UNIT | | TO THE CURB MUST BE IN COMPLIANCE WITH THE | | MANUFACTURER'S INSTALLATION RECOMMENDATIONS. PLEASE | | PROVIDE EVIDENCE THAT THIS IS AN ACCEPTABLE METHOD BY | | THE MANUFACTURER- OTHERWISE THE PRODUCT WARRANTY MAY BE | | VOIDED. | | 2) SUBMIT PRODUCT DATA (CUT) SHEETS FOR THE RTU CURB |
|