Plan Review Notes For Permit 15060717 |
Permit Number |
15060717 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-07-29 12:04:53 | 2ND REVIEW: FBC 2010 MECHANICAL | | | | 1) THE LOCATION OF RTU #3 SHOWN IN THE NEW STRUCTURAL | | 8-1/2 X 11 PLAN SHEET SUBNITTAL DOES NOT MATCH THE | | RE-LOCATION ON THE M-1 PLAN. | | 2) THE SUBMITTED 8-1/2 STRUCTURAL DRAWING INDICATES | | "EXISITING CURB TO DECK ATTACHMENT TO REMAIN". HOW IS | | THIS POSSIBLE IF THE UNIT HAS BEEN RELOCATED TO A SPOT | | WHERE THERE WASN'T A PRIOR CURB OR ROOF OPENING | | EXISTING? PLEASE PROVIDE COMPLETE STRUCTUAL DRAWINGS | | FOR THE INSTALLATION. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|