Plan Review Notes
Plan Review Notes For Permit 15060717
Permit Number 15060717
Review Stop M
Sequence Number 2
Notes
Date Text
2015-07-29 12:04:532ND REVIEW: FBC 2010 MECHANICAL
  
 1) THE LOCATION OF RTU #3 SHOWN IN THE NEW STRUCTURAL
 8-1/2 X 11 PLAN SHEET SUBNITTAL DOES NOT MATCH THE
 RE-LOCATION ON THE M-1 PLAN.
 2) THE SUBMITTED 8-1/2 STRUCTURAL DRAWING INDICATES
 "EXISITING CURB TO DECK ATTACHMENT TO REMAIN". HOW IS
 THIS POSSIBLE IF THE UNIT HAS BEEN RELOCATED TO A SPOT
 WHERE THERE WASN'T A PRIOR CURB OR ROOF OPENING
 EXISTING? PLEASE PROVIDE COMPLETE STRUCTUAL DRAWINGS
 FOR THE INSTALLATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER