2015-06-17 12:40:48 | 1ST REVIEW: FBC 2010 MECHANICAL | | | | 1) THE REVISION INDICATES THE RELOCATION OF RTU #3 FROM | | THE ROOF ABOVE THE EXERCISE AREA TO THE ROOF ABOVE THE | | LOCKER/REST ROOM AREA: PROVIDE REVISIONS TO THE | | STRUCTURAL DRAWINGS AND DETAILS. | | 2) REVISE THE ENERGY CALCULATIONS TO SHOW THE CHANGE | | FROM THE 15 SEER YORK RTU'S TO THE 13 SEER CARRIER | | RTU'S | | | | CHRISTOPHER COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|