Plan Review Notes For Permit 15060694 |
Permit Number |
15060694 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-06-22 14:41:16 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) IS THE FITNESS CENTERAND EQUIPMENT EXISTING AND | | PREVIOUSLY APPROVED AND IS BEING REMODLED OR IS IT A | | NEW PROJECT. PROVIDE AN INDICATING NOTE. | | | | 2) THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF | | THE 5TH EDITION OF FLORIDA FIRE PREVENTION CODE | | INCLUDING THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND | | ALL OTHER APPLICABLE CODES OR STANDARDS. | | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS | | OF NFPA 13, 2010 EDITION. | | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | NFPA 72, 2010 EDITION. | | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | NFPA 241, 2009 EDITION. | | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS | | OF NFPA 10, 2010 EDITION. | | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. | | | | 3) PROVIDE NOTE INDICATING FIRE ALARM WORK UNDER | | SEPARATE SHOP DRAWINGS. | | | | 4) PROVIDE A DOOR SCHEDULE OR NOTE FOR THE INSTALL OF | | DOORS AT THE NEW LOCATIONS. | | |
|