2015-06-21 10:51:11 | |
| BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15060694 |
| ADD: 622 N. FLAGLER DR. / FITNESS CENTER |
| CONT: BRANCH CONSTRUCTION |
| TEL: ( 561)833-6206 |
| E-MAIL: |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: SUN.JUNE 21/ 2015 |
| ACTION: DENIED |
| |
| 1) SHEET A1 DOES NOT SHOW ENOUGH DETAIL AS TO THE |
| LOCATION IN THE BUILDING: |
| 1A) PLEASE PROVIDE THE SQ. FOOTAGE OF THE FITNESS |
| CENTER AND OCCUPANT LOAD TAKEN FOR THIS AREA, THERE IS |
| ONLY ONE MEANS OF EGRESS INTO AND OUT OF THIS AREA. 15 |
| SQ. FEET /OCCUPANT W/ NO EXERCISE EQUIPMENT, 50 SQ. |
| FEET W/ EQUIPMENT FBC-B TABLE 1004.1.1. |
| |
| 1B) IS THE FITNESS CENTER ON THE SAME FLOOR AS |
| RESIDENTIAL UNITS OR IS THERE RESIDENTIAL OCCUPANCY |
| BENEATH THESE UNITS? AND THE THIRD QUESTION IS IN THE |
| REMODELING OF THE FITNESS CENTER THE FLOOR BEING |
| REPAIRED WITH MATCHING FINISH OR IS THE FLOOR BEING |
| REPLACED. |
| NOTE IF THE FLOOR IS BEING REPAIRED NO ACTION IS |
| REQUIRED. IF THERE IS RESIDENTIAL UNITS EITHER ON THE |
| SAME FLOOR, OR THE FLOOR BENEATH AND NEW FLOOR FINISHES |
| ARE BEING INSTALLED EITHER MARBLE TILE OR WOOD FLOORING |
| THEN THE FOLLOWING (3) CODE SECTION SHALL APPLY; |
| |
| 1B)(1) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 1B)(2) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 1B)(3) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |