Plan Review Notes
Plan Review Notes For Permit 15060694
Permit Number 15060694
Review Stop B
Sequence Number 1
Notes
Date Text
2015-06-21 10:51:11 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060694
 ADD: 622 N. FLAGLER DR. / FITNESS CENTER
 CONT: BRANCH CONSTRUCTION
 TEL: ( 561)833-6206
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUN.JUNE 21/ 2015
 ACTION: DENIED
  
 1) SHEET A1 DOES NOT SHOW ENOUGH DETAIL AS TO THE
 LOCATION IN THE BUILDING:
 1A) PLEASE PROVIDE THE SQ. FOOTAGE OF THE FITNESS
 CENTER AND OCCUPANT LOAD TAKEN FOR THIS AREA, THERE IS
 ONLY ONE MEANS OF EGRESS INTO AND OUT OF THIS AREA. 15
 SQ. FEET /OCCUPANT W/ NO EXERCISE EQUIPMENT, 50 SQ.
 FEET W/ EQUIPMENT FBC-B TABLE 1004.1.1.
  
 1B) IS THE FITNESS CENTER ON THE SAME FLOOR AS
 RESIDENTIAL UNITS OR IS THERE RESIDENTIAL OCCUPANCY
 BENEATH THESE UNITS? AND THE THIRD QUESTION IS IN THE
 REMODELING OF THE FITNESS CENTER THE FLOOR BEING
 REPAIRED WITH MATCHING FINISH OR IS THE FLOOR BEING
 REPLACED.
 NOTE IF THE FLOOR IS BEING REPAIRED NO ACTION IS
 REQUIRED. IF THERE IS RESIDENTIAL UNITS EITHER ON THE
 SAME FLOOR, OR THE FLOOR BENEATH AND NEW FLOOR FINISHES
 ARE BEING INSTALLED EITHER MARBLE TILE OR WOOD FLOORING
 THEN THE FOLLOWING (3) CODE SECTION SHALL APPLY;
  
 1B)(1) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B)(2) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1B)(3) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  