Plan Review Notes For Permit 15060686 |
Permit Number |
15060686 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2016-05-10 19:00:08 | PLAN | | REVIEW COMMENTS | | | | 4TH REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SOME OF THE INFORMATION LISTED IN THE ENERGY | | COMPLIANCE FORMS IS INCORRECT OR MISSING. THE DESIGN | | LOCATION ON THE FORMS IS LISTED AS FORT LAUDERDALE AND | | THE PROJECT IS IN WEST PALM BEACH FL IN PALM BEACH | | COUNTY. THE SECOND FLOOR 2 X 6 WOOD FRAME WALLS ARE NOT | | LISTED. ONLY ONE WATER HEATER IS LISTED ON THE FORMS | | AND TWO ARE SHOWN ON THE PLANS (ONE ON EACH FLOOR). THE | | INSULATED ADJACENT WOOD FRAME WALLS BETWEEN THE GARAGE | | AND THE CONDITIONED SPACE IS NOT LISTED. THE RAISED | | FLOOR OF THE MASTER BED ROOM AREA ABOVE THE GARAGE IS | | NOT LISTED ON THE ENERGY FORMS. THE INSULATION IN THE | | CEILING OF THE FIRST FLOOR BEDROOM THAT IS BELOW THE | | SECOND FLOOR COVERED PORCH DOES NOT APPEAR TO BE | | INCLUDED ON THE FORMS. FBC ENERGY CONSERVATION SEC. | | R405 | | | | 2) THE ENERGY FORM 405-10 IS REQUIRED TO BE SIGNED AND | | DATED BY THE OWNER/AGENT. FBC ENERGY CONSERVATION | | SECTION R405. | | | | | | | | | | | | |
|