2016-01-19 16:13:14 | PLAN |
| REVIEW COMMENTS |
| |
| 3RD REVIEW: FBC 2010 |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY MECHANICAL |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: (SAME COMMENTS AS |
| LAST REVIEW. COMMENTS HAVE NOT BEEN ADDRESSED.) |
| |
| 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. |
| ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| THE PERSON RESPONSIBLE FOR THE DESIGN. THE PRINTED |
| NAME, SIGNATURE AND LICENSE NUMBER OF THE SYSTEM |
| DESIGNER IS REQUIRED ON THE MECHANICAL DRAWINGS. |
| |
| 2) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT |
| BEDROOMS. TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING |
| THE RETURN TRANSFER 1-1/2 TIMES THE CROSS SECTIONAL |
| AREA (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE |
| ROOM OR SPACE IT IS SERVING AND THE DOOR HAVING AT |
| LEAST AN UNRESTRICTED 1 INCH UNDERCUT TO ACHIEVE PROPER |
| RETURN AIR BALANCE. THERE IS NO RETURN SHOWN FOR THE |
| FIRST FLOOR MASTER BEDROOM AND THE TRANSFER DUCT FOR |
| BEDROOM #2 IS NOT 1-1/2 TIMES THE CROSS SECTIONAL AREA |
| (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM. |
| THE TRANSFER DUCT FOR THE SECOND FLOOR MASTER BEDROOM |
| IS NOT 1-1/2 TIMES THE CROSS SECTIONAL AREA (SQUARE |
| INCHES) OF THE 12" SUPPLY DUCT SUPPLYING THE MASTER |
| SUITE ( ALL SUPPLY AIR INTO THE MASTER SUITE SHALL BE |
| INCLUDED ). |
| |
| 3) SOME OF THE INFORMATION LISTED IN THE ENERGY |
| COMPLIANCE FORMS IS INCORRECT OR MISSING. THERE ARE 5 |
| BEDROOMS LISTED ON THE FORMS/SIZING CALCULATIONS AND |
| ONLY 4 BEDROOMS ARE SHOWN ON THE PLANS. ONLY ONE WATER |
| HEATER IS LISTED ON THE FORMS AND TWO ARE SHOWN ON THE |
| PLANS (ONE ON EACH FLOOR). THE INSULATED WALLS AND |
| FLOOR/CEILING ASSEMBLY ADJACENT TO THE GARAGE ARE NOT |
| LISTED ON THE ENERGY FORMS. THE INSULATION IN THE |
| CEILING OF THE FIRST FLOOR BEDROOM THAT IS BELOW THE |
| SECOND FLOOR COVERED PORCH DOES NOT APPEAR TO BE |
| INCLUDED ON THE FORMS. FBC ENERGY CONSERVATION SEC. |
| R405 |
| |
| 4) THE ENERGY FORM 405-10 IS REQUIRED TO BE SIGNED AND |
| DATED BY THE OWNER/AGENT. FBC ENERGY CONSERVATION |
| SECTION R405. |
| |
| |
| |
| |
| |
| |