Plan Review Notes
Plan Review Notes For Permit 15060686
Permit Number 15060686
Review Stop E
Sequence Number 3
Notes
Date Text
2016-01-21 10:35:44YOUR RESUBMITTAL ADDRESSING THE PREVIOUSLY MENTIONED
 DEFICIENCIES HAS ONCE AGAIN FAILED THE ELECTRICAL
 REVIEW AS INDICATED BELOW. NEW COMMENTS IF ANY PROMPTED
 BY ANOTHER REVIEW, MOST LIKELY DUE TO YOUR FAILURE TO
 SUBMIT A RESPONSE LETTER (NARRATIVE) ADDRESSING THE
 REQUIRED CORRECTIONS WILL BE NUMBERED IN CONTINUATION
 OF ANY PREVIOUS COMMENTS.
  
 THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE
 EDITION OF THE NEC, (NATIONAL ELECTRICAL CODE) AND THE
 FBC, (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF
 WEST PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL.
  
 IN A TELEPHONE CONVERSATION WITH MR. LES CZACZYK OF LCA
 I WAS PROMPTED TO ISSUE THIS WITH A PROVISO, BUT LATER
 REALIZED THAT NONE OF THE TRADES COMMENTS FROM PRIOR
 REVIEWS HAD BEEN ADDRESSED SO I DECIDED TO ISSUE THE
 NOTES FOR THE REQUIRED CORRECTIONS AS PREVIOUSLY
 MENTIONED SO THAT THE PLANS CAN ALL GET CORRECTED
 PROPERLY.
  
 1. CARBON MONOXIDE DETECTORS HAVE NOT ADDED TO THE
 PLANS. REVISE PLANS TO SHOW PROPER COVERAGE.
 2. COMMENTS 5 & 6 REFER TO LOAD CALCS AND PANEL
 SCHEDULES. THE PANEL SCHEDULE AS INDICATED ON THE
 DRAWINGS REFLECTS CIRCUITS FOR THE CONDENSING UNITS IN
 PANEL ?A? AS WELL AS MAIN FOR SAME IN THE SPLIT BUS
 EXTERIOR PANEL. BEING THAT YOU HAVE THIS ARRANGEMENT,
 LOAD CALCS WILL VARY FROM PANEL SCHEDULES. SUBMIT AS
 REQUIRED.
 3. THE PREVIOUSLY DISCUSSED MISSING INTER-SYSTEM
 BONDING TERMINAL PER NEC 250.94 HAS NOT BEEN ADDED TO
 THE SERVICED RISER.
 4. ADD A NOTE TO THE PLANS ADDRESSING THE NEC 406.8(B)
 REQUIREMENT FOR WEATHER RATED RECEPTACLES IN WET
 LOCATIONS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE
 THE CORRECTIONS ARE ON ALONG WITH THE STANDARD CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  