2016-01-21 10:35:44 | YOUR RESUBMITTAL ADDRESSING THE PREVIOUSLY MENTIONED |
| DEFICIENCIES HAS ONCE AGAIN FAILED THE ELECTRICAL |
| REVIEW AS INDICATED BELOW. NEW COMMENTS IF ANY PROMPTED |
| BY ANOTHER REVIEW, MOST LIKELY DUE TO YOUR FAILURE TO |
| SUBMIT A RESPONSE LETTER (NARRATIVE) ADDRESSING THE |
| REQUIRED CORRECTIONS WILL BE NUMBERED IN CONTINUATION |
| OF ANY PREVIOUS COMMENTS. |
| |
| THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE |
| EDITION OF THE NEC, (NATIONAL ELECTRICAL CODE) AND THE |
| FBC, (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF |
| WEST PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. |
| |
| IN A TELEPHONE CONVERSATION WITH MR. LES CZACZYK OF LCA |
| I WAS PROMPTED TO ISSUE THIS WITH A PROVISO, BUT LATER |
| REALIZED THAT NONE OF THE TRADES COMMENTS FROM PRIOR |
| REVIEWS HAD BEEN ADDRESSED SO I DECIDED TO ISSUE THE |
| NOTES FOR THE REQUIRED CORRECTIONS AS PREVIOUSLY |
| MENTIONED SO THAT THE PLANS CAN ALL GET CORRECTED |
| PROPERLY. |
| |
| 1. CARBON MONOXIDE DETECTORS HAVE NOT ADDED TO THE |
| PLANS. REVISE PLANS TO SHOW PROPER COVERAGE. |
| 2. COMMENTS 5 & 6 REFER TO LOAD CALCS AND PANEL |
| SCHEDULES. THE PANEL SCHEDULE AS INDICATED ON THE |
| DRAWINGS REFLECTS CIRCUITS FOR THE CONDENSING UNITS IN |
| PANEL ?A? AS WELL AS MAIN FOR SAME IN THE SPLIT BUS |
| EXTERIOR PANEL. BEING THAT YOU HAVE THIS ARRANGEMENT, |
| LOAD CALCS WILL VARY FROM PANEL SCHEDULES. SUBMIT AS |
| REQUIRED. |
| 3. THE PREVIOUSLY DISCUSSED MISSING INTER-SYSTEM |
| BONDING TERMINAL PER NEC 250.94 HAS NOT BEEN ADDED TO |
| THE SERVICED RISER. |
| 4. ADD A NOTE TO THE PLANS ADDRESSING THE NEC 406.8(B) |
| REQUIREMENT FOR WEATHER RATED RECEPTACLES IN WET |
| LOCATIONS. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE |
| THE CORRECTIONS ARE ON ALONG WITH THE STANDARD CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |