Plan Review Notes For Permit 15060686 |
Permit Number |
15060686 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-07-22 15:50:16 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | | 1. PER FBC-R 315, YOU SHALL HAVE A CO (CARBON MONOXIDE) | | DETECTOR WITHIN 10' OF EACH BEDROOM DOOR | | 2. PER NEC 314.27, ALL CEILING MOUNTED LUMINAIRE | | OUTLETS SHALL BE LISTED TO SUPPORT 50 LBS. | | 3. PER NEC 210.52(A)(2)(3), A FLOOR OUTLET SHALL BE | | PLACED ALONG THE FLOOR LINE OF THE STAIR RAIL ON THE | | SECOND FLOOR. | | 4. PER FBC-E 404, A MINIMUM OF 50% OF PERMANENTLY | | INSTALLED LIGHTING FIXTURES SHALL HAVE HIGH-EFFICIENCY | | LAMPS. | | 5. PER NEC 408.4, PROVIDE AN ACCURATE AND SITE SPECIFIC | | CIRCUIT IDENTIFICATION LIST, (PANEL SCHEDULE) | | 6. PER NEC 220.82, PROVIDE SITE SPECIFIC LOAD CALCS TO | | VERIFY SERVICE CAPACITY/REQUIREMENTS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | PREVIOUSLY REVIEWED SHEETS. | | |
|