2015-07-22 15:50:16PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. PER FBC-R 315, YOU SHALL HAVE A CO (CARBON MONOXIDE)
 DETECTOR WITHIN 10' OF EACH BEDROOM DOOR
 2. PER NEC 314.27, ALL CEILING MOUNTED LUMINAIRE
 OUTLETS SHALL BE LISTED TO SUPPORT 50 LBS.
 3. PER NEC 210.52(A)(2)(3), A FLOOR OUTLET SHALL BE
 PLACED ALONG THE FLOOR LINE OF THE STAIR RAIL ON THE
 SECOND FLOOR.
 4. PER FBC-E 404, A MINIMUM OF 50% OF PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL HAVE HIGH-EFFICIENCY
 LAMPS.
 5. PER NEC 408.4, PROVIDE AN ACCURATE AND SITE SPECIFIC
 CIRCUIT IDENTIFICATION LIST, (PANEL SCHEDULE)
 6. PER NEC 220.82, PROVIDE SITE SPECIFIC LOAD CALCS TO
 VERIFY SERVICE CAPACITY/REQUIREMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  