Plan Review Notes
Plan Review Notes For Permit 15060642
Permit Number 15060642
Review Stop E
Sequence Number 1
Notes
Date Text
2015-06-27 16:59:266/27/2015
 PROJECT: 3916 GREEWOOD RENNOVATION
 PERMIT#: 14020194
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW REVISION #15060882
 ACTION: DENIED
  
 PERMIT# 14020194 INSPECTION RESULTS DATED 03/03/2014
 NOTE FROM DOUG HARVEY:
 STOP WORK ORDER ISSUED. WORK BEING DONE
 IN ALL TRADES. PLANS AND COMPLETE
 PERMITS NEEDED. NO WORK AND NO POWER
 UNTIL FULL PERMIT IS ISSUED AND
 COMPLETED. ELECTRICAL NOT READY. NO
 WIRES AT SERVICE.
  
 PERMIT #14020194 IS NOT CURRENTLY EXPIRED. AS A RESULT
 A NEW PERMIT APPLICATION IS NOT REQUIRED. THE SCOPE OF
 WORK HAS CHANGED. THE PERMIT APPLICATION IS CHANGED TO
 REVISION #15060882.
  
 1) INDICATE WHERE THE SMOKE DETECTORS ARE INSTALLED.
 WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314 AND 315.
  
 2) NEC 210.12, 406.11
 ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 3) NEC 210.52(C)(3) BATHROOM BRANCH CIRCUITS. IN
 ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY
 OTHER PARTS OF THIS SECTION, AT LEAST ONE 20-AMPERE
 BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM
 RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER
 OUTLETS.
 3A) NEC 210.52 (D) BATHROOMS. IN DWELLING UNITS, AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN
 BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH
 BASIN. THE RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL
 OR PARTITION THAT IS ADJACENT TO THE BASIN OR BASIN
 COUNTERTOP, OR INSTALLED ON THE SIDE OR FACE OF THE
 BASIN CABINET NOT MORE THAN (12 IN.) BELOW THE
 COUNTERTOP.
  
 4) NEC 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL
 (A) DWELLING UNITS. ALL 125-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE RECEPTACLES INSTALLED IN THE LOCATIONS
 SPECIFIED IN (1) THROUGH (8) SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL.
 (1) BATHROOMS
  
 5) WPB AMENDEMNTS TO THE FBC 107.3.5.3
 PROVIDE A PANEL SCHEDULE AND LOAD CALCULATION. EVERY
 CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. NEC 408.4
  
 6) NEC 110.9
 VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS HAS A
 FAULT CURRENT RATING THAT IS SUFFICIENT AT NOMINAL
 CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED.
  
 7) FBC-EXISTING 708.3 RESIDENTIAL OCCUPANCIES.
 IN GROUP R-2, R-3, AND R-4 OCCUPANCIES AND BUILDINGS
 REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL,
 THE REQUIREMENTS OF SECTIONS 708.3.1 THROUGH 708.3.7
 SHALL BE APPLICABLE ONLY TO WORK AREAS LOCATED WITHIN A
 DWELLING UNIT. INDICATE WHAT IS EXISTING TO REMAIN AND
 WHAT IS PROPOSED TO BE NEW. IT IS NOT CLEAR FROM WHAT
 IS SUBMITTED WHAT IS EXISTING AND WHAT IS PROPOSED.
  
 8) WPB AMENDMENTS TO FBC 107.3.1
 TWO COPIES OF ALL PLANS AND SPECIFICATIONS ARE REQUIRED
 FOR SUBMITTAL WITH AN APPLICATION FOR PERMIT. ONCE
 REVIEWED AND READY FOR ISSUANCE, ONE SET TO BE RETAINED
 BY THE BUILDING OFFICIAL FOR THE PURPOSE OF RECORD
 KEEPING AND THE OTHER TO BE RETURNED TO THE APPLICANT
 UPON ISSUANCE OF THE PERMIT.
  
 9) WPB AMENDMENTS TO FBC 107.2.1
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 10) WPB AMENDMENTS TO FBC 107.2.1.4
 QUALITY OF BUILDING PLANS. BUILDING PLANS SHALL BE
 DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL
 PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
2015-06-23 15:03:11NO ELECTRICAL SHOWN ON PLANS.