Plan Review Notes For Permit 15060642 |
Permit Number |
15060642 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-06-23 15:00:29 | ****CORRECTIONS**** | | ART LANGE - BUILDING INSPECTOR | | 561-805-6667 [email protected] | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 6/23/15 | | | | 1. BUILDING PERMIT VALUE TOO LOW. FBC 109.3 BUILDING | | PERMIT VALUATION. FOR PERMITTING PURPOSES, VALUATION OF | | BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE | | TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, | | INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND | | DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT; | | EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY | | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL | | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, | | MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE | | CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET | | BY THE BUILDING OFFICIAL. | | | | 2. TRULITE SINGLE HUNG WINDOW NOTICE OF ACCEPTANCE | | (NOA) IS EXPIRED. PLEASE SUBMIT TWO UDATED NOA'S. | | | | 3. PERMIT APPLICATION HAS ELECTRICAL WORK CHECKED. NO | | ELECTRICAL WORK IS SHOWN ON PLANS. PERMIT APPLICATION | | ALSO SHOWS NEW CLOSETS ADDED. THIS IS NOT SHOWN ON | | PLANS. PLEASE REVISE PLANS TO SHOW ALL WORK TO BE | | COMPLETED UNDER THIS PERMIT. | | |
|