Plan Review Notes For Permit 15060612 |
Permit Number |
15060612 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-08-21 16:28:43 | 2ND REVIEW: FBC 2010 | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | 561-805-6711 | | [email protected] | | | | | | COMMENTS: | | 1.OCCUPANCY OF A DAYCARE IS AN I-4 FBC SEC. 308.5 | | 2.PLEASE CLARIFY. ON A-1 YOU STATE TOTAL SF AS 1400/20 | | SF/OCC.=70 AND YOU HAVE YOUR NET SF AS 840 /35 =24. ON | | P-1 YOU STATE 1900/100 SF/OCC =19 .SHOW HOW YOU | | DETERMENT 35 PEOPLE STATED IN YOUR LETTER.PER WPB | | AMEND.TO FBC 2010 SEC107.2.13. | | 3. TOILET IN STAFF BATHROOM IS NOT VENTED PROPERLY IT | | SHOULD BE VENTED BY LAV VENT OR INDIVIDUAL VENT. PER | | FBCP SEC.901.2.1 | | 4.FLOOR DRAIN SHALL HAVE A TRAP PRIMER. PER FBCP 1002.4 | | |
|