Plan Review Notes For Permit 15060612
Permit Number 15060612
Review Stop P
Sequence Number 2
Notes
Date Text
2015-08-21 16:28:432ND REVIEW: FBC 2010
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 561-805-6711
 [email protected]
  
  
 COMMENTS:
 1.OCCUPANCY OF A DAYCARE IS AN I-4 FBC SEC. 308.5
 2.PLEASE CLARIFY. ON A-1 YOU STATE TOTAL SF AS 1400/20
 SF/OCC.=70 AND YOU HAVE YOUR NET SF AS 840 /35 =24. ON
 P-1 YOU STATE 1900/100 SF/OCC =19 .SHOW HOW YOU
 DETERMENT 35 PEOPLE STATED IN YOUR LETTER.PER WPB
 AMEND.TO FBC 2010 SEC107.2.13.
 3. TOILET IN STAFF BATHROOM IS NOT VENTED PROPERLY IT
 SHOULD BE VENTED BY LAV VENT OR INDIVIDUAL VENT. PER
 FBCP SEC.901.2.1
 4.FLOOR DRAIN SHALL HAVE A TRAP PRIMER. PER FBCP 1002.4
  