Plan Review Notes
Plan Review Notes For Permit 15060612
Permit Number 15060612
Review Stop M
Sequence Number 2
Notes
Date Text
2015-08-21 12:13:252ND REVIEW: FBC 2010 MECHANICAL
 PERMIT #15060612
 8/21/15
  
 1) AC SYSTEM SIZING CALCULATIONS ARE REQUIRED IN
 ACCORDANCE WITH SECTION 503.2.1 FBC-10 ENERGY
 CONSERVATION. HOW WAS AC-2 SIZED? WAS A CALCULATION RUN
 ON THE BUILDING, AND WAS AC-1 TAKEN INTO ACCOUNT?
 PLEASE SUBMIT TWO COPIES OF COOLING AND HEATING LOADS
 DETERMINED IN ACCORDANCE WITH THE ASHRAE/ACCA STANDARD
 183 OR ACCA MANUAL N.
 2) REFER TO TABLE 101.4.1 FBC-10 ENERGY CONSERVATION:
 THE PROPOSED CHANGE OF OCCUPANCY PROJECT SHALL BE IN
 COMPLIANCE WITH THE CURRENT ENERGY CODE WITH MINIMUM
 EFFICIENCIES MET FOR ENVELOPE COMPONENTS, EQUIPMENT,
 AND LIGHTING BEING CHANGED. PROVIDE TWO COPIES OF
 EITHER FORM 502 OR 506 TO VERIFY COMPLIANCE- REFER TO
 TABLE 103.2.1.
 3) PROVIDE EXHAUST VENTILATION FOR THE JANITOR'S CLOSET
 IN ACCORDANCE WITH TABLE 6-4 ASHRAE 62.1-07. THE
 EXHAUST RATE BY THE TABLE SHALL BE 1.00 CFM PER SQ. FT.
 4) AS PREVIOUSLY REQUESTED PROVIDE STRUCTURAL DETAILS
 FOR THE CONDENSER PAD AND TIE-DOWN ENGINEERING FOR THE
 CONDENSER. THE SUBMITTED 8-1/2 X 11 COPIED PLAN DETAIL
 IS NOT ACCEPTABLE BECAUSE- A) IT A POOR COPY BARELY
 LEGIBLE. B) IT HAS COPIED (PLAGIRIZED) FROM ANOTHER
 PLAN AND IS NOT SITE SPECIFIC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  