Plan Review Notes
Plan Review Notes For Permit 15060612
Permit Number 15060612
Review Stop E
Sequence Number 2
Notes
Date Text
2015-09-28 17:09:38PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. YOU SHALL SUBMIT A COMPLETE AND SITE SPECIFIC RISER
 DIAGRAM AS INDICATED IN NEC 210.5. THERE SHALL BE A
 NOTE RELATING TO THE ARC-FAULT REQUIREMENT OF 110.16 AS
 WELL.
 2. YOU SHALL ALSO PROVIDE LOAD CALCULATIONS AS REQUIRED
 IN NEC 220.16
 3. YOU SHALL INDICATE WITH CERTAINTY THE LOCATION OF
 THE SERVICE EQUIPMENT AS REQUIRED BY NEC 230.70
 4. YOU SHALL INDICATE ON THE FLOOR PLAN THE LOCATION OF
 THE ELECTRICAL PANELS AS REQUIRED BY NEC 240.24
 5. EVERY COMMERCIAL ESTABLISHMENT SHALL HAVE A
 DEDICATED SIGN OUTLET ABOVE EVERY DOOR USED FOR
 PEDESTRIAN ACCESS AS MENTIONED IN NEC 600.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  