Plan Review Notes For Permit 15060612 |
Permit Number |
15060612 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-07-09 14:51:34 | 1ST REVIEW: FBC 2010 MECHANICAL | | PERMIT #15060612 7/9/15 | | | | 1) A MAIN RETURN AIR GRILL OR LOUVERED DOOR FOR THE AHU | | CLOSET IS REQUIRED PER SECTION 601.4. REVISE THE PLANS | | ACCORDINGLY. PLEASE NOTE THAT THE DOUBLE CLOSET DOORS | | SHALL BE CONSTRUCTED OF METAL IN COMPLIANCE WITH | | SECTION 602.2, AND ALL MATERIALS FORMING THE ENCLOSURE | | OR PLENUM CHAMBER SHALL BE NON-COMBUSTIBLE AND SEALED | | WITH APPROVED MATERIALS- 603.1. | | 2. PROVIDE THE TYPE AND SIZE OF BATH EXHAUST DUCTS, AND | | SHOW THE DUCT RUNS AND TERMINATION LOCATIONS- SECTION | | 501.2.1. | | 3) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE | | CONDENSER PAD, AND WIND LOAD ENGINEERING FOR TIE DOWN | | OF THE CONDENSER- SECTION 301.12. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|