2015-07-09 14:51:341ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15060612 7/9/15
  
 1) A MAIN RETURN AIR GRILL OR LOUVERED DOOR FOR THE AHU
 CLOSET IS REQUIRED PER SECTION 601.4. REVISE THE PLANS
 ACCORDINGLY. PLEASE NOTE THAT THE DOUBLE CLOSET DOORS
 SHALL BE CONSTRUCTED OF METAL IN COMPLIANCE WITH
 SECTION 602.2, AND ALL MATERIALS FORMING THE ENCLOSURE
 OR PLENUM CHAMBER SHALL BE NON-COMBUSTIBLE AND SEALED
 WITH APPROVED MATERIALS- 603.1.
 2. PROVIDE THE TYPE AND SIZE OF BATH EXHAUST DUCTS, AND
 SHOW THE DUCT RUNS AND TERMINATION LOCATIONS- SECTION
 501.2.1.
 3) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE
 CONDENSER PAD, AND WIND LOAD ENGINEERING FOR TIE DOWN
 OF THE CONDENSER- SECTION 301.12.
  