Plan Review Notes
Plan Review Notes For Permit 15060612
Permit Number 15060612
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-06-22 16:41:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) DOOR SWING. WHERE SERVING A ROOM OR AREA WITH AN
 OCCUPANT LOAD OF 50 OR MORE THE DOOR SHALL SWING IN THE
 DIRECTION OF EGRESS TRAVEL. THE FRONT DOOR AND THE
 VESTIBULE DOOR SHALL SWING IN THE DIRECTION OF EGRESS.
  
 2) PROVIDE A SITE PLAN SHOWING THAT THE PROPOSED EXITS
 LEAD TO A PUBLIC WAY.
  
 3) NFPA 101 16.3.2.PROTECTION FROM HAZARDS. 16.3.2.1
 ROOMS OR SPACES FOR THE STORAGE, PROCESSING, OR USE OF
 MATERIALS SPECIFIED IN 16.3.2.1 (1) THROUGH (3) SHALL
 BE OPROTECTED IN ACCORDANCE WITH THE FOLLOWING:
 (1) SEPARATION FROM THE REMIADER OF THE BUILDING BY
 FIRE BARRIERS HAVING A MINIMUM 1-HOUR FIRE RESISTIVE
 RATING, OR PROTECTION OF SUCH ROOMS BY AUTIOMATICE
 EXTINGUSHING SYSTEMS AS SPECIFIED IN
 SECTION 8.7 IN THE FOLLOWING AREAS:
 (D) JANITOR CLOSETS.
 PROVIDE FIRE RESISTIVE WALSS AND DOOR TO THE PROPOSED
 JANITOR CLOSET.
  
 4) PROVIDE INFORMATION PERTAINING TO THE OTHER CAMPUS
 BUILDINGS RELATING TO EXISTING FIRE SPRINKLER OF FIRE
 ALARM. CONNECTION TO EXISTING BUILDINGS THAT ARE FULLY
 SPRINKLERED MAY REQUIRE THAT THIS BUILDING BE
 SPRINKLERED DUE TO IT BEING ATTACHED. THE FIRE ALARM
 MAY BE REQUIRED TO BE CONNECTED TO THE CAMPUS FIRE
 ALARM IF EXISTING.
  
 5) PROVIDE THE OCCUPANCIES OF THE OTHER CAMPUS
 BUILDINGS. DESCRIBE WHAT IS BEING CONDUCTED IN EACH OF
 THE BUILDINGS.
  
  