Date |
Text |
2015-07-13 08:59:12 | 7/13/2015 |
| PROJECT: GRATTITUDE HOUSE |
| PERMIT#:15060612 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC, |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| COMMENTS: |
| |
| 1) INDICATE LOCATION OF SERVICE. NEC 230.70 |
| |
| 2) INDICATE THE LOCATION OF THE ELECTRICAL PANEL. NEC |
| 240.24 |
| |
| 4) PROVIDE A LOAD CALCULATION IN ACCORDANCE WITH THE |
| NEC 220. |
| |
| 5) A FIRE ALARM SYSTEM IS REQUIRED AND SHALL BE |
| SUBMITTED AS A SEPARATE APPLICATION WITH COMPLETE SHOP |
| DRAWING AND MANUFACTURER SUBMITTALS IN ACCORDANCE WITH |
| THE FBC 436.7 AND 907 |
| |
| 6) ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH |
| GROUND FAULT CIRCUIT INTERRUPTER PROTECTION. NEC 422.52 |
| |
| 7) INDICATE THE REQUIRED DISCONNECT FOR THE WATER |
| HEATER. NEC 422.31 |
| |
| 8) INDICATE THE DISCONNECTING MEANS LOCATED WITHIN |
| SIGHT AND READILY ACCESSIBLE FROM THE A/C EQUIPMENT. |
| NEC 440.14 |
| |
| 9) INDICATE THE LOCATION OF THE A/C CU'S AND THE |
| REQUIRED DISCONNECTS IN ACCORDANCE WITH THE NEC 440.14 |
| |
| 10) INDICATE THE REQUIRED GFI OUTLETL WITHIN SIGHT OF |
| AND ACCESSIBLE TO A/C EQUIPMENT. NEC 210.63 |
| |
| 11) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| RESISTANT NEC 406.11 |
| |
| 12) INDICATE THE REQUIRED EMERGENCY AND EXIT LIGHTING |
| ON THE ELECTRICAL LIGHTING PLANS IN ACCORDANCE WITH THE |
| NEC 700.12 AND 700.16 |
| |
| 13) THE PANEL SCHEDULE INDICATES A TOTAL OF FOUR AHU'S |
| IDENTIFIED AS AHU #1, AHU #1, AHU #2, AND AHU#3. THERE |
| ARE ONLY TWO CU'S. THEY ARE IDENTIFIED AS A/C COMP #2, |
| AND A/C COMP #3 THERE ARE ONLY TWO AHU'S INDICATED ON |
| THE FLOOR PLAN. PLEASE CLARIFY AND INDICATE THE ACTUAL |
| CIRCUITRY AND DISCONNECTS FOR ALL A/C UNITS. FBC |
| 107.3.2 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |