Plan Review Notes
Plan Review Notes For Permit 15060603
Permit Number 15060603
Review Stop P
Sequence Number 1
Notes
Date Text
2015-06-19 10:29:071) SUBMIT A ROOF PLAN SHOWING THE LOCATION OF THE ROOF
 DRAINS AND SHOW THE SQUARE FOOTAGE OF THE ROOF THAT IS
 BEING DRAINED INTO EACH DRAIN.WPB AMEND. TO 2010 FBC
 SEC. 107.2.1.
 2) THE SIZING OF THE ROOF DRAINS AND ALL VERTICAL AND
 HORIZONTAL PIPING SHALL BE SIZED IN ACCORDANCE WITH
 TABLES 1106.2 (1) & 1106.3 FOR A RAINFALL RATE OF 5
 INCHES PER HOUR.
 3) INDICATE TYPE OF PIPING TO INSTALLED. IF PVC, IT
 SHALL BE SUPPORTED AT 4 FT.INTERVALS HORIZONTALLY AND
 10 FT. INTERVALS VERTICALLY. INDICATE ON THE PLANS HOW
 THE PIPE WILL BE SUPPORTED.
 4) SUBMIT DETAILS FOR SECONDARY (EMERGENCY) DRAINAGE
 PER 2010 FPC SEC.1107.1.
 5) INDICATE IF THERE IS A PARAPET WALL ON THIS PROJECT.
 IF SO, ONE-HALF THE AREA OF ANY VERTICAL WALL THAT
 DIVERTS RAINWATER TO THE ROOF SHALL BE ADDED TO THE
 PROJECTED ROOF AREA PER 2010 FPC SEC.1106.4.
 6) SHOW THE TERMINATION POINT OF EACH DRAIN. THE
 VERTICAL LEADERS/CONDUCTORS SHALL DISCHARGE A MINIMUM
 OF ONE (1) FOOT FROM THE STRUCTURE SIDEWALL PER THE
 2010 FBC SEC.1503.7. SUBMIT A PLAN SHOWING THE
 TERMINATION/DISCHARGE POINTS OF THE LEADERS/CONDUCTORS.
 WPB AMEND. TO 2010 FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
2015-06-19 09:38:14ROUTED TO PLUMBING/CC


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved