2015-06-12 14:54:08 | BUILDING PLAN REVIEW |
| |
| 2010 FLORIDA BUILDING CODE W? |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 1ST REVIEW |
| DENIED |
| |
| 1) IS THIS APPLICATION FOR THE TEMPORARY INSTALLATION |
| OF A CONSTRUCTION MODULAR BUILDING OR SALES TRAILER FOR |
| 6 MONTHS, OR LONGER? |
| |
| THE 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, 102.2 BUILDING. THE FOLLOWING |
| BUILDINGS, STRUCTURES AND FACILITIES ARE EXEMPT FROM |
| THE FLORIDA BUILDING CODE AS PROVIDED BY LAW, AND ANY |
| FURTHER EXEMPTIONS SHALL BE AS DETERMINED BY THE |
| LEGISLATURE AND PROVIDED BY LAW: |
| |
| (E) MOBILE OR MODULAR STRUCTURES USED AS TEMPORARY |
| OFFICES, EXCEPT THAT THE PROVISIONS OF PART V (SECTION |
| 553.501-553.513, FLORIDA STATUTES) RELATING TO |
| ACCESSIBILITY BY PERSONS WITH DISABILITIES, AND PERMITS |
| SHALL BE REQUIRED FOR STRUCTURAL SUPPORT AND TIE DOWN, |
| ELECTRICAL SUPPLY, AND ALL UTILITY CONNECTIONS TO SUCH |
| MOBILE OR MODULAR STRUCTURES. |
| |
| 2) NO PLANS WERE SUBMITTED FOR THE ACCESSIBLE PARKING |
| SPACE, ACCESS AISLE, ACCESSIBLE ROUTE TO THE OFFICE, |
| RAMP, STAIRS, LANDING, GAURDRAIL/ HANDRAIL SYSTEM. |
| SEE ACC CODE, 405.1-10. |
| |
| 3) INADEQUATE PLANS WERE SUBMITTED SUCH THAT |
| DETERMINATION OF THE INTENDED STRUCTURE AS APPROVED BY |
| AN OUTSIDE AGENCY COULD BE MADE. |
| |
| 4) IT IS PRESUMED A LOCALLY ENGINEERED FOUNDATION PLAN |
| MAY BE REQUIRED. |
| |