Plan Review Notes For Permit 15060568 |
Permit Number |
15060568 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-06-29 11:43:36 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THE EXTENT OF THE REMODEL OR REVISION IS UNCLEAR AND | | DOES NOT INDICATE SUFFICIENT DETAIL TO ADDRESS LIFE | | SAFETY CONCERNS OF THE PROPOSED PROJECT. | | | | 2) WITH THE PROPOSED CEILING WORK, INDICATED IF THE THE | | AREA IS SPRINKLERED OR HAS FIRE ALARM DEVICES | | | | 3) INDICATED THAT ANY SPRINKLER AND/OR FIRE ALARM WORK | | SHALL BE SUBMITTED UNDER SEPARATE SHOP DRAWINGS. THE | | LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE SPRINKLER | | SHALL REMAIN ACTIVE THROUGHOUT THE CONSTRUCTION PERIOD. | | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | AND COMPLETE PROTECTION IS RETURNED. | | | | 4) INDICATED THAT THE PROPOSED PROJECT SHALL MEET THE | | REQUIREMENTS OF THE 5TH EDITION OF FLORIDA FIRE | | PREVENTION CODE INCLUDING THE 2012 EDITION OF NFPA 1 | | AND NFPA 101 AND ALL OTHER APPLICABLE CODES OR | | STANDARDS. | | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS | | OF NFPA 13, 2010 EDITION. | | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | NFPA 72, 2010 EDITION. | | | | | | |
|