Plan Review Notes
Plan Review Notes For Permit 15060568
Permit Number 15060568
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-06-29 11:43:36THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE EXTENT OF THE REMODEL OR REVISION IS UNCLEAR AND
 DOES NOT INDICATE SUFFICIENT DETAIL TO ADDRESS LIFE
 SAFETY CONCERNS OF THE PROPOSED PROJECT.
  
 2) WITH THE PROPOSED CEILING WORK, INDICATED IF THE THE
 AREA IS SPRINKLERED OR HAS FIRE ALARM DEVICES
  
 3) INDICATED THAT ANY SPRINKLER AND/OR FIRE ALARM WORK
 SHALL BE SUBMITTED UNDER SEPARATE SHOP DRAWINGS. THE
 LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE SPRINKLER
 SHALL REMAIN ACTIVE THROUGHOUT THE CONSTRUCTION PERIOD.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 4) INDICATED THAT THE PROPOSED PROJECT SHALL MEET THE
 REQUIREMENTS OF THE 5TH EDITION OF FLORIDA FIRE
 PREVENTION CODE INCLUDING THE 2012 EDITION OF NFPA 1
 AND NFPA 101 AND ALL OTHER APPLICABLE CODES OR
 STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
  
  
  