 PROJECT: RULMAN 400 N FLAGLER #2102
 PERMIT#:15060568
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC,
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER ONE,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 THE DESCRIPTION OF WORK ON THE PERMIT APPLICATION
 APPEARS TO READ "REMOVE EXISTING BATHROOM AND REDO 4
 NEW ONES, MASTER & GUEST BATHROOM" BUT THE PLANS ONLY
 SHOW AN EXTREMELY VAGUE SCOPE OF WORK IN ONE BATH.
 CLARIFY WPB AMEND. TO 2010 FBC SEC. 107.2.1.
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) PROVIDE A FIXTURE SCHEDULE FOR LIGHTING FIXTURES TO
 BE INSTALLED INDICATING COMPLIANCE WITH THE NEC
 110.3(B), 410.10(D) AND FBC-ENERGY 502.3.8
  
 2) AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN
 BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH
 BASIN. 210.52 (D) BATHROOMS. INDICATE THE REQUIRED
 RECEPTACLE IN THE BATHROOM BY THE SINK.
 RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN (1)
 THROUGH (8) SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL. (1) BATHROOMS
  
 3) PROVIDE A PANEL SCHEDULE INDICATING COMPLIANCE WITH
 THE NEC 210.11(C)(3) AND 408.4
  
 4) VERIFY OR INDICATE COMPLIANCE WITH THE FBC REGARDING
 THE EXISTIANCE OR INSTALLATION OF INTERCONNECTED SMOKE
 DETECTORS. WHEN ALTERATIONS, REPAIRS, OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
 FBC-RESIDENTIAL 314 AND 315
  
 5) INDICATE HOW THE LIGHTING WILL BE CONTROLLLED AND
 THE LOCATION OF SWITCHES. INDICATE WHETHER SWITCHES ARE
 NEW OR EXISTING.
  
 6) INDICATE COMPLIANCE WITH THE NEC. ALL NEW GENERAL
 PURPOSE OUTLETS MUST BE TAMPER RESISTANT AND AFCI
 PROTECTED. NEC 210.12, 406.11
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,