| PROJECT: RULMAN 400 N FLAGLER #2102 |
| PERMIT#:15060568 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC, |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER ONE, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| THE DESCRIPTION OF WORK ON THE PERMIT APPLICATION |
| APPEARS TO READ "REMOVE EXISTING BATHROOM AND REDO 4 |
| NEW ONES, MASTER & GUEST BATHROOM" BUT THE PLANS ONLY |
| SHOW AN EXTREMELY VAGUE SCOPE OF WORK IN ONE BATH. |
| CLARIFY WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| |
| REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| COMMENTS: |
| |
| 1) PROVIDE A FIXTURE SCHEDULE FOR LIGHTING FIXTURES TO |
| BE INSTALLED INDICATING COMPLIANCE WITH THE NEC |
| 110.3(B), 410.10(D) AND FBC-ENERGY 502.3.8 |
| |
| 2) AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN |
| BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH |
| BASIN. 210.52 (D) BATHROOMS. INDICATE THE REQUIRED |
| RECEPTACLE IN THE BATHROOM BY THE SINK. |
| RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN (1) |
| THROUGH (8) SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER |
| PROTECTION FOR PERSONNEL. (1) BATHROOMS |
| |
| 3) PROVIDE A PANEL SCHEDULE INDICATING COMPLIANCE WITH |
| THE NEC 210.11(C)(3) AND 408.4 |
| |
| 4) VERIFY OR INDICATE COMPLIANCE WITH THE FBC REGARDING |
| THE EXISTIANCE OR INSTALLATION OF INTERCONNECTED SMOKE |
| DETECTORS. WHEN ALTERATIONS, REPAIRS, OR ADDITIONS |
| REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE |
| ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| FBC-RESIDENTIAL 314 AND 315 |
| |
| 5) INDICATE HOW THE LIGHTING WILL BE CONTROLLLED AND |
| THE LOCATION OF SWITCHES. INDICATE WHETHER SWITCHES ARE |
| NEW OR EXISTING. |
| |
| 6) INDICATE COMPLIANCE WITH THE NEC. ALL NEW GENERAL |
| PURPOSE OUTLETS MUST BE TAMPER RESISTANT AND AFCI |
| PROTECTED. NEC 210.12, 406.11 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |