Plan Review Notes
Plan Review Notes For Permit 15060568
Permit Number 15060568
Review Stop B
Sequence Number 1
Notes
Date Text
2015-06-27 14:10:28BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060568
 ADD: 400 N. FLSGLER DR. SUITE 2102
 CONT: MARYJULI CONSTRUCTION
 TEL: (561)386-6032
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. JUNE 27/2015
 ACTION: DENIED
  
 1) THE PLANS DO NOT HAVE ANY DESIGN CRITERIA TO WHAT
 CODE HAS THE PLANS BEEN DRAWN, UNDER THE EXISTING
 BUILDING CODE THE DESIGNER OF RECORD NEEDS TO INDICATE
 ON THE PLANS THE COMPLIANCE METHOD FOR THIS DESIGN.
 2010 EXST. BLDG. CODE 101.5.
  
 2) THE PLANS DO NOT INDICATE THE BUILDING TYPE NOR THE
 RESTRICTIONS ON TYPE I TYPE II CONSTRUCTION. 2010 FBC-B
 603..1 ALLOWABLE MATERIALS.
  
 3) THE PLANS INDICATE THERE IS TO BE RAISED CEILINGS IN
 THE MASTER BATH, NO DETAILS AS TO HOW THE EXISTING
 CEILING/ SOFFIT IS HUNG NOR HOW THE NEW RAISED CEILINGS
 ARE TO BE BUILT. 107.3.5.1.1 MINIMUM PLAN REVIEW
 CRITERIA FOR COMMERCIAL BUILDINGS. TYPE OF MATERIALS
 FOR FRAMING MEMBERS, SIZE OF FRAMING MEMBERS, GAUGE,
 SPACING, IF STIFF BACKS ARE REQUIRED TYPE OF FINISH
 MATERIAL AND THICKNESS. PLEASE PROVIDE THE FINISH
 ELEVATION ABOVE THE FINISH FLOOR.
  
 4) THE PERMIT APPLICATION INDICATES TO RENOVATE
 BATHROOMS, IF THE FLOORING IS BEING REMOVED PLEASE
 PROVIDE COMPLIANCE WITH:
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION
  
 4A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 4C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 5) THE PLANS INDICATE A NEW SHOWER STALL PLEASE PROVIDE
 THE TYPE OF BACKING TO BE REPLACED FOR THE PLACEMENT OF
 TILE. 2010 FBC-B
 2509.2 BASE FOR TILE SURFACES.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  