2015-06-27 14:10:28 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15060568 |
| ADD: 400 N. FLSGLER DR. SUITE 2102 |
| CONT: MARYJULI CONSTRUCTION |
| TEL: (561)386-6032 |
| E-MAIL: |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: SAT. JUNE 27/2015 |
| ACTION: DENIED |
| |
| 1) THE PLANS DO NOT HAVE ANY DESIGN CRITERIA TO WHAT |
| CODE HAS THE PLANS BEEN DRAWN, UNDER THE EXISTING |
| BUILDING CODE THE DESIGNER OF RECORD NEEDS TO INDICATE |
| ON THE PLANS THE COMPLIANCE METHOD FOR THIS DESIGN. |
| 2010 EXST. BLDG. CODE 101.5. |
| |
| 2) THE PLANS DO NOT INDICATE THE BUILDING TYPE NOR THE |
| RESTRICTIONS ON TYPE I TYPE II CONSTRUCTION. 2010 FBC-B |
| 603..1 ALLOWABLE MATERIALS. |
| |
| 3) THE PLANS INDICATE THERE IS TO BE RAISED CEILINGS IN |
| THE MASTER BATH, NO DETAILS AS TO HOW THE EXISTING |
| CEILING/ SOFFIT IS HUNG NOR HOW THE NEW RAISED CEILINGS |
| ARE TO BE BUILT. 107.3.5.1.1 MINIMUM PLAN REVIEW |
| CRITERIA FOR COMMERCIAL BUILDINGS. TYPE OF MATERIALS |
| FOR FRAMING MEMBERS, SIZE OF FRAMING MEMBERS, GAUGE, |
| SPACING, IF STIFF BACKS ARE REQUIRED TYPE OF FINISH |
| MATERIAL AND THICKNESS. PLEASE PROVIDE THE FINISH |
| ELEVATION ABOVE THE FINISH FLOOR. |
| |
| 4) THE PERMIT APPLICATION INDICATES TO RENOVATE |
| BATHROOMS, IF THE FLOORING IS BEING REMOVED PLEASE |
| PROVIDE COMPLIANCE WITH: |
| |
| BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION |
| |
| 4A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 4B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 4C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 5) THE PLANS INDICATE A NEW SHOWER STALL PLEASE PROVIDE |
| THE TYPE OF BACKING TO BE REPLACED FOR THE PLACEMENT OF |
| TILE. 2010 FBC-B |
| 2509.2 BASE FOR TILE SURFACES. |
| |
| 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |