Plan Review Notes
Plan Review Notes For Permit 15060537
Permit Number 15060537
Review Stop E
Sequence Number 1
Notes
Date Text
2015-06-20 14:54:49APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 WPC AMENDMENTS TO FBC 110.3 REQUIRED INSPECTIONS: (B)1.
 : UNDERGROUND INSPECTION (INCLUDING BONDING AND
 GROUND). TO BE MADE AFTER TRENCHES OR DITCHES ARE
 EXCAVATED, CONDUIT OR CABLE IS INSTALLED, AND BEFORE
 ANY BACKFILL IS PUT IN PLACE.
  
 REVISE YOUR PLANS PRIOR TO FIRST ELECTRICAL INSPECTION
 AND PROVIDE TO THE ELECTRICAL INSPECTOR ON SITE IN
 RESPONSE TO THE FOLLOWING REVIEW COMMENTS:
  
 1) PROVIDE A SITE PLAN TO INDICATE THE LOCATION OF THE
 ELECTRICAL SERVICE AND THE TRANSFORMER. WPB AMENDMENT
 TO THE FBC 107.3.5.1.2 ELECTRICAL
  
 2) PROVIDE A GROUNDING DETAIL. WPB AMENDMENT TO THE FBC
 107.3.5.1.2 ELECTRICAL
 .
 3) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. FBC, WPB
 AMENDMENTS 107.2.1
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]