Plan Review Notes For Permit 15060526 |
Permit Number |
15060526 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-06-14 05:20:37 | 1) INDICATE ON THE PLANS WHAT TYPE OF OPERATIONS THE | | HAND SINK & THREE COMPARTMENT SINK WILL SERVE. THE | | THREE COMPARTMENT SINK MAY BE REQUIRED TO DISCHARGE | | THROUGH A GREASE REMOVAL DEVICE OR A GREASE INTERCEPTOR | | / GREASE REMOVAL DEVICE.. | | 2010 FPC SEC. 1003.3.1, WPB AMEND. TO 2010 FBC SEC. | | 107.2.1. | | 2) IS THE FLOOR SINK & HAND SINK EXISTING? INDICATE ON | | PLAN. | | 3) SUBMIT A FLOOR PLAN SHOWING THE LAYOUT & LOCATION OF | | THESE FIXTURES. | | 4) SHOW THE PIPING FOR THE TANKLESS WATER HEATER ON THE | | PLANS. IS IT GAS OR ELECTRIC? SUBMIT MANUFACTURER'S | | SPECIFICATION SHEETS FOR THE TANKLESS WATER HEATER. A | | SEPARATE ELECTRIC PERMIT WILL ALSO BE REQUIRED. IF GAS, | | SUBMIT A GAS DRAWING FOR REVIEW. | | 5) CITY RECORDS DO NOT SHOW ANY PREVIOUS PERMITS FOR A | | HAND SINK, THREE COMPARTMENT SINK. | | | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|