Plan Review Notes
Plan Review Notes For Permit 15060526
Permit Number 15060526
Review Stop P
Sequence Number 1
Notes
Date Text
2015-06-14 05:20:371) INDICATE ON THE PLANS WHAT TYPE OF OPERATIONS THE
 HAND SINK & THREE COMPARTMENT SINK WILL SERVE. THE
 THREE COMPARTMENT SINK MAY BE REQUIRED TO DISCHARGE
 THROUGH A GREASE REMOVAL DEVICE OR A GREASE INTERCEPTOR
 / GREASE REMOVAL DEVICE..
 2010 FPC SEC. 1003.3.1, WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 2) IS THE FLOOR SINK & HAND SINK EXISTING? INDICATE ON
 PLAN.
 3) SUBMIT A FLOOR PLAN SHOWING THE LAYOUT & LOCATION OF
 THESE FIXTURES.
 4) SHOW THE PIPING FOR THE TANKLESS WATER HEATER ON THE
 PLANS. IS IT GAS OR ELECTRIC? SUBMIT MANUFACTURER'S
 SPECIFICATION SHEETS FOR THE TANKLESS WATER HEATER. A
 SEPARATE ELECTRIC PERMIT WILL ALSO BE REQUIRED. IF GAS,
 SUBMIT A GAS DRAWING FOR REVIEW.
 5) CITY RECORDS DO NOT SHOW ANY PREVIOUS PERMITS FOR A
 HAND SINK, THREE COMPARTMENT SINK.
  
  