2015-06-20 08:19:03 | 1) THE GAS SIZING TABLE FOR THE GASTITE PE PIPE THAT |
| HAS BEEN IDENTIFIED ON THE DOCUMENTS IS SHOWN AS A GAS |
| PRESSURE OF 10 PSI, YET THE FIRST PAGE OF THE GAS |
| DRAWING NOTES AN 11" W.C. CLARIFY. WPB AMEND. TO 2010 |
| FBC SEC. 107.3.5.1.5. |
| 2) INDICATE THE PSI ON THE SYSTEM BETWEEN THE TANK AND |
| THE 2ND STAGE REGULATOR AND FROM THE 2ND STAGE |
| REGULATOR TO THE GENERATOR. THE ONLY PRESSURE INDICATED |
| ON THE PLANS IS 11" W.C. CLARIFY. |
| 3)THE TWO TABLES REFERENCED ON THE GAS RISER DRAWING |
| ARE FOR NATURAL GAS. SUBMIT THE CORRECT TABLES FOR THE |
| LP GAS AND THE PRESSURES. |
| 4) THE DOCUMENTS FROM TIE-DOWN ENGINEERING SHALL BEAR |
| THE SEAL AND WET SIGNATURE OF THE ENGINEER PER THE FL. |
| ADMIN. CODE SEC. 61G15-23.002. THE SUBMITTED DOCUMENTS |
| ARE COPIES. |
| 5) THIS AN ABOVE GROUND TANK AND YOU HAVE ALSO |
| SUBMITTED SPECS FOR AN UNDERGROUND TANK. REMOVE ANY |
| DOCUMENTS THAT DO NOT APPLY. WPB AMEND. TO 2010 FBC |
| SEC. 107.2.1. |
| 6) THE TANK IS LOCATED IN A TRAFFIC AREA. SUBMIT |
| DETAILS AS TO HOW THE TANK IS GOING TO BE PROTECTED IN |
| ACCORDANCE WITH NFPA 58 SEC.6.6.6 (D). IF BOLLARDS ARE |
| USED SUBMIT DETAILS. SHOW THE HEIGHT OF THE BOOLARDS |
| ABOVE GROUND, THE BURIAL DEPTH BELOW GROUND, THE |
| DIAMETER, CENTER TO CENTER SPACING, ETC.NFPA 58 SEC. |
| 6.6.1.2. |
| 7) THE NOTES WRITTEN ON THE SURVEY ARE DONE IN PECIL. |
| PENCILED PLANS ARE UNACCEPTABLE.SUBMIT TWO COPIES OF |
| PLANS THAT CANNOT BE ALTERED. |
| 8) INDICATE THE CORRESPONDING EHD OF THE FLEX LINE FROM |
| THE 2ND STAGE REGULATOR TO THE GENERATOR. |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| 561-805-6692 |