2015-06-20 08:19:031) THE GAS SIZING TABLE FOR THE GASTITE PE PIPE THAT
 HAS BEEN IDENTIFIED ON THE DOCUMENTS IS SHOWN AS A GAS
 PRESSURE OF 10 PSI, YET THE FIRST PAGE OF THE GAS
 DRAWING NOTES AN 11" W.C. CLARIFY. WPB AMEND. TO 2010
 FBC SEC. 107.3.5.1.5.
 2) INDICATE THE PSI ON THE SYSTEM BETWEEN THE TANK AND
 THE 2ND STAGE REGULATOR AND FROM THE 2ND STAGE
 REGULATOR TO THE GENERATOR. THE ONLY PRESSURE INDICATED
 ON THE PLANS IS 11" W.C. CLARIFY.
 3)THE TWO TABLES REFERENCED ON THE GAS RISER DRAWING
 ARE FOR NATURAL GAS. SUBMIT THE CORRECT TABLES FOR THE
 LP GAS AND THE PRESSURES.
 4) THE DOCUMENTS FROM TIE-DOWN ENGINEERING SHALL BEAR
 THE SEAL AND WET SIGNATURE OF THE ENGINEER PER THE FL.
 ADMIN. CODE SEC. 61G15-23.002. THE SUBMITTED DOCUMENTS
 ARE COPIES.
 5) THIS AN ABOVE GROUND TANK AND YOU HAVE ALSO
 SUBMITTED SPECS FOR AN UNDERGROUND TANK. REMOVE ANY
 DOCUMENTS THAT DO NOT APPLY. WPB AMEND. TO 2010 FBC
 SEC. 107.2.1.
 6) THE TANK IS LOCATED IN A TRAFFIC AREA. SUBMIT
 DETAILS AS TO HOW THE TANK IS GOING TO BE PROTECTED IN
 ACCORDANCE WITH NFPA 58 SEC.6.6.6 (D). IF BOLLARDS ARE
 USED SUBMIT DETAILS. SHOW THE HEIGHT OF THE BOOLARDS
 ABOVE GROUND, THE BURIAL DEPTH BELOW GROUND, THE
 DIAMETER, CENTER TO CENTER SPACING, ETC.NFPA 58 SEC.
 6.6.1.2.
 7) THE NOTES WRITTEN ON THE SURVEY ARE DONE IN PECIL.
 PENCILED PLANS ARE UNACCEPTABLE.SUBMIT TWO COPIES OF
 PLANS THAT CANNOT BE ALTERED.
 8) INDICATE THE CORRESPONDING EHD OF THE FLEX LINE FROM
 THE 2ND STAGE REGULATOR TO THE GENERATOR.
  