Plan Review Notes
Plan Review Notes For Permit 15060508
Permit Number 15060508
Review Stop E
Sequence Number 1
Notes
Date Text
2015-07-08 16:14:35PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE CORRECTIONS NOTED..
  
 THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS
 RESUBMITTED FOR A SECOND REVIEW:
 1. PROVIDE AN EASIER TO UNDERSTAND RISER DIAGRAM. THIS
 DIAGRAM SHALL INDICATE LINE SIDE OF METER WHETHER
 OVERHEAD OR UNDERGROUND.
 2. YOU SHALL PROVIDE LOAD CALCS FOR THE COMPLETE
 RESIDENCE, NOT JUST THE GENERATOR LOAD.
 3. FROM THE SUBMITTED RISER, IT APPEARS THAT BOTH
 PANELS ARE ON THE LOAD SIDE OF THE ATS.
 4. PER NEC ALL CONDUCTORS INSIDE AN UNDERGROUND RACEWAY
 SHALL BE LISTED FOR WET LOCATION AND THHN IS NOT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  
2015-06-18 11:17:32SENT TO GENERATOR BIN