2015-07-08 16:14:35 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | THE CORRECTIONS NOTED.. | | | | THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS | | RESUBMITTED FOR A SECOND REVIEW: | | 1. PROVIDE AN EASIER TO UNDERSTAND RISER DIAGRAM. THIS | | DIAGRAM SHALL INDICATE LINE SIDE OF METER WHETHER | | OVERHEAD OR UNDERGROUND. | | 2. YOU SHALL PROVIDE LOAD CALCS FOR THE COMPLETE | | RESIDENCE, NOT JUST THE GENERATOR LOAD. | | 3. FROM THE SUBMITTED RISER, IT APPEARS THAT BOTH | | PANELS ARE ON THE LOAD SIDE OF THE ATS. | | 4. PER NEC ALL CONDUCTORS INSIDE AN UNDERGROUND RACEWAY | | SHALL BE LISTED FOR WET LOCATION AND THHN IS NOT. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | PREVIOUSLY REVIEWED SHEETS. | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | | | THANK YOU | | | 2015-06-18 11:17:32 | SENT TO GENERATOR BIN |
|