Plan Review Notes
Plan Review Notes For Permit 15060473
Permit Number 15060473
Review Stop M
Sequence Number 1
Notes
Date Text
2015-07-06 08:03:501ST REVIEW: FBC 2010 MECHANICAL
  
 1) REFERENCE TABLE 403.3 MINIMUM VENTILATION RATES:
 PROVIDE VENTILATION CALCULATIONS FOR THE NEW EXERCISE
 ROOMS. INDICATE ON THE PLAN THE REQUIRED O/A CFM'S PER
 THE TABLE AND THE AMOUNT OF CFM'S PROVIDED BY THE
 EXISTING SYSTEM. PROVIDE DRAWINGS AND DETAILS FOR ANY
 REQUIRED MODIFICATIONS TO THE EXISTING SYSTEM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved