Plan Review Notes
Plan Review Notes For Permit 15060449
Permit Number 15060449
Review Stop B
Sequence Number 1
Notes
Date Text
2015-06-11 17:51:58BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060449
 ADD: 107 FLAGLER PROMENADE S.
 CONT: STORM ROOFING
 TEL: ( 561) 689-0268
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 1) THE TYPE OF UNDERLAYMENT HAS NOT BEEN IDENTIFIED.
 THE MIAMI-DADE NOA 12-0308.20 LIMITATION 3.4 MINIMUM
 UNDERLAYMENT SHALL BE IN COMPLIANCE WITH THE APPLICABLE
 ROOFING APPLICATION STANDARDS LISTED IN SECTION 4.1
 HEREIN.
  
 2) MIAMI-DADE NOA 12-0228.18 3M 2-COMPONENT FOAM ROOF
 TILE ADHESIVE AH-160 LIMITATION # 3 THE MINIMUM
 UNDERLAYMENT SHALL BE IN COMPLIANCE WITH THE ROOFING
 APPLICATION STANDARD RAS 120.
  
 3) MIAMI-DADE NOA 12-0228.18 3M 2-COMPONENT FOAM ROOF
 TILE ADHESIVE AH-160 THE ADHESIVE PLACEMENT FROM TABLE
 # 1 HAS NOT BEEN IDENTIFIED, AS TO TILE PROFILE
 PLACEMENT DETAIL IF SINGLE PADDY OR TWO PADDY SYSTEM.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  