2015-06-11 17:51:58 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15060449 |
| ADD: 107 FLAGLER PROMENADE S. |
| CONT: STORM ROOFING |
| TEL: ( 561) 689-0268 |
| E-MAIL: [email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE |
| CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND |
| DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, |
| FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND |
| RESISTANCE RATING THAT ARE REQUIRED TO BE |
| INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL |
| INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR |
| THE SPECIFIC SITE. |
| |
| 1) THE TYPE OF UNDERLAYMENT HAS NOT BEEN IDENTIFIED. |
| THE MIAMI-DADE NOA 12-0308.20 LIMITATION 3.4 MINIMUM |
| UNDERLAYMENT SHALL BE IN COMPLIANCE WITH THE APPLICABLE |
| ROOFING APPLICATION STANDARDS LISTED IN SECTION 4.1 |
| HEREIN. |
| |
| 2) MIAMI-DADE NOA 12-0228.18 3M 2-COMPONENT FOAM ROOF |
| TILE ADHESIVE AH-160 LIMITATION # 3 THE MINIMUM |
| UNDERLAYMENT SHALL BE IN COMPLIANCE WITH THE ROOFING |
| APPLICATION STANDARD RAS 120. |
| |
| 3) MIAMI-DADE NOA 12-0228.18 3M 2-COMPONENT FOAM ROOF |
| TILE ADHESIVE AH-160 THE ADHESIVE PLACEMENT FROM TABLE |
| # 1 HAS NOT BEEN IDENTIFIED, AS TO TILE PROFILE |
| PLACEMENT DETAIL IF SINGLE PADDY OR TWO PADDY SYSTEM. |
| |