Plan Review Notes For Permit 15060336 |
Permit Number |
15060336 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-06-23 13:42:46 | 1ST REVIEW: FBC 2010 MECHANICAL | | | | 1) THE ORIGINAL ENERGY CALCULATIONS SUBMITTED FOR THE | | NEW ADDITION UNDER PERMIT #14090756 INDICATE AN | | EXISTING 13 SEER SYSTEM. PLEASE REVISE THE CALCULATIONS | | TO SHOW THE NEW 16 SEER SYSTEM. | | 2) PROVIDE AC LOAD CALCULATIONS FOR THE NEW ADDITION AC | | SYSTEM PER SECTION 403.6.1 FBC-10 ENERGY CONSERVATION. | | THERE WERE NO CALCS SUBMITTED WITH THE ADDITION PLANS. | | 3) PROVIDE DETAILS FOR INSTALLATIONS OF THE CONDENSER | | PAD AND TIE DOWN OF THE CONDENSER- SECTION M1307.2.1 | | FBC-10 RESIDENTIAL. PLEASE NOTE THE CONDENSER SHALL BE | | INSTALLED AT OR ABOVE THE FLOOD ELEVATION HEIGHT- | | SECTION R322.1.6. | | | | CHRISTOPHER COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | |
|