Plan Review Notes
Plan Review Notes For Permit 15060336
Permit Number 15060336
Review Stop M
Sequence Number 1
Notes
Date Text
2015-06-23 13:42:461ST REVIEW: FBC 2010 MECHANICAL
  
 1) THE ORIGINAL ENERGY CALCULATIONS SUBMITTED FOR THE
 NEW ADDITION UNDER PERMIT #14090756 INDICATE AN
 EXISTING 13 SEER SYSTEM. PLEASE REVISE THE CALCULATIONS
 TO SHOW THE NEW 16 SEER SYSTEM.
 2) PROVIDE AC LOAD CALCULATIONS FOR THE NEW ADDITION AC
 SYSTEM PER SECTION 403.6.1 FBC-10 ENERGY CONSERVATION.
 THERE WERE NO CALCS SUBMITTED WITH THE ADDITION PLANS.
 3) PROVIDE DETAILS FOR INSTALLATIONS OF THE CONDENSER
 PAD AND TIE DOWN OF THE CONDENSER- SECTION M1307.2.1
 FBC-10 RESIDENTIAL. PLEASE NOTE THE CONDENSER SHALL BE
 INSTALLED AT OR ABOVE THE FLOOD ELEVATION HEIGHT-
 SECTION R322.1.6.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER