Plan Review Notes
Plan Review Notes For Permit 15060333
Permit Number 15060333
Review Stop P
Sequence Number 2
Notes
Date Text
2015-08-04 06:27:131) COMPLY WITH 2010 FBC-R R4101.6.3 FOR WATER VELOCITY.
 2) SUBMIT DETAILS FOR ENTRAPMENT PROTECTION. FBC-R
 SEC.R4101.6.6.
 3) WATER SUPPLY SHALL COMPLY WITH 2010 FBC-R SEC.
 R4101.9.
 4) COMPLY WITH 2010 FBC- R SEC.R4101.10.WHERE IS THE
 POOL DISCHARGE/WASTE LINE?
 5) THE GENERAL CONTRACTOR SHALL ONLY CONSTRUCT THE POOL
 SHELL PER F.S. 489.113 (3)(C).
 6) THE POOL PIPING PLAN SHOWS A "FLOOR DRAIN" BUT THERE
 IS NO PIPING TO IT. CLARIFY.
 7) THE POOL RETURN IS SHOWN AS 2 INCH ON THE PLUMBING
 SCHEDULE AND AS 1 1/2 INCH ON THE RETURN DETAIL. WHICH
 IS IT? CLARIFY.
 8) SUBMIT MANUF. SPECIFICATION SHEETS FOR THE MAIN
 DRAIN COVER.THE COVER SHALL COMPLY WITH ASME/ANSI
 A112.19.8 PER APSP 7 SEC.4.5.
 9) SUPPLY THE TOTAL DYNAMIC HEAD CALCULATIONS TO
 DETERMINE THE MAXIMUM FLOW RATE OF THE PUMP.APSP 7
 SEC.4.4.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]