Plan Review Notes For Permit 15060333
Permit Number 15060333
Review Stop P
Sequence Number 1
Notes
Date Text
2015-06-12 08:06:111) THE SUBMITTED PLANS ARE SEVERELY DEFICIENT WITH THE
 REQUIRED CODE INFORMATION THAT A THOROUGH,
 COMPREHENSIVE PLUMBING REVIEW COULD NOT BE
 ACCOMPLISHED. THE DESIGN OF THE SWIMMING POOL SHALL
 COMPLY WITH THE FOLLOWING STANDARDS AND CODE SECTIONS:
 2010 FBC-R SECS.R4101.6.1,
 ANSI/NSPI3, ANSI/NSPI 4, ANSI/NSPA 5,ANSI/NSPI 6,
 ANSI/APSP-7.
 2) COMPLY WITH 2010 FBC-R R4101.6.3 FOR WATER VELOCITY.
 SUBMIT DETAILS.
 3) SUBMIT DETAILS FOR ENTRAPMENT PROTECTION. FBC-R
 SEC.R4101.6.6.
 4) SUBMIT DETAILS, MANUF. SPEC SHEETS & PUMP
 PERFORMANCE CURVE.2010 WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 5) COMPLY W/ 201 FBC-R SEC.R4101.7.1.
 6) COMPLY W/ 2010 FBC- R SEC.R4101.8.2.
 7) WATER SUPPLY SHALL COMPLY WITH 2010 FBC-R SEC.
 R4101.9.
 8) COMPLY WITH 2010 FBC- R SEC.R4101.10.
 9) COMPL WITH 2010 FBC-R SEC.R4101.20.
 10) COMPLY WITH 2010 FBC-R SEC.R4101.21.2.
 11) THE PLANS SHALL COMPLY WITH FL. ADMIN. CODE RULE
 61G15-23.002 (2)(B)(3).
 12) THE GENERAL CONTRACTOR SHALL ONLY CONSTRUCT THE
 POOL SHELL PER F.S. 489.113 (3)(C).
 13) IDENTIFY ALL THE RETURNS ON THE PIPING PLAN. 2010
 WPB AMEND. TO 2010 FBC SEC. 107.2.1.
  
 NOTE: ONE SET OF PLANS IS BEING RETAINED BY THE
 BUILDING DIVISION.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  