Plan Review Notes For Permit 15060319 |
Permit Number |
15060319 |
|
Review Stop |
Z |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-10-28 15:52:10 | CONDITIONAL PASS - CONTRACTOR PROCEEDS AT OWN RISK | | UNTIL CONDITIONS SUFFICIENTLY ADDRESSED. | | | | THE FOLLOWING ITEMS SHALL BE CORRECTED/ADDRESSED AS | | PART OF A PERMIT REVISION PRIOR TO THE FINAL INSPECTION | | (104) APPROVAL. | | | | 1) THE DOCK INSTALLATION PLANS SHALL CLEARLY DESIGNATE | | THE NEW SOUTHERN BOUNDARY OF THE LEASE LINE. THE PIERS, | | NOR ANY BOATS DOCKED AT THE PIERS MAY EXTEND PAST THE | | LEASE LINE. | | | | 2) THE DEP PERMIT AND THE SITE PLAN APPROVED PLANS SHOW | | PIERS THAT ARE 160 FEET LONG (MAXIMUM), WHILE THE | | MARINETEK PLANS SHOW THE LONGEST PIERS AT 160 FEET 5 | | INCHES. PLEASE EXPLAIN. | | | | 3) THE PROPOSED IMPROVEMENT PLAN BY BOLCHOZ MARINE | | ADVISOR'S, INC., SHOWS THE SOUTHERN MOST ANCHOR PILE AT | | THE END OF THE DOCK, YET THE MAINETEK PLANS SHOW THE | | PILE WITHIN THE DOCK. ALL PLANS SHALL SHOW THE SAME | | CONDITION. | | | | 4) SHEET E-1 SHOWS A SLIP E200. THIS SLIP IS NOT | | APPROVED AS PART OF THE DEP APPROVAL AND SHALL BE | | REMOVED FROM THE PLANS. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|