2015-06-25 10:17:50 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15060319 |
| ADD: 400 N. FLAGLER DR. |
| CONT:MURRAY LOGAN CONSTRUCTION |
| TEL: (561)686-3948 |
| E-MAIL: |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: TUES. OCT27/ 2015 |
| ACTION: DENIED |
| |
| 1) THE STRUCTURAL DESIGN FOR THE FLOATING DOCK AND |
| FINGER PIERS APPERA TO BE PRELIMINARY PLANS. SEE THE |
| FOLLOWING SHEETS ARE NOT SIGNED NOR SEALED. |
| 1A) THEORETICAL FREEBOARD (NOMINAL) AT DEAD LOAD |
| WITHOUT UTILITIES |
| 1B) DOCK E EXTENSION |
| 1C) FIXING SET INSTALATION SY |
| 1D) CONNECTION DETAIL (DET1) |
| 1E) SUPER YAUCHT BOLLARD 7.5 TN |
| 1F) MEGA YAUCHT BOLLARD 10 TN |
| PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN |
| CODE 61G15-23.002 ENGINEERS |
| |
| SUBMITTED ALSO 1 BOOKLET OF CALCULATIONS BY CLE |
| ENGINEERING. PLEASE NOTE THIS BOOK IS 1 1/2 INCHES |
| THICK OF VARIOUS CALCULATIONS AND DOCUMENTS. PLEASE |
| PROVIDE EITHER 2 OF THESE BOOKS SIGNED AND |
| SEALEDCOMPLYING WITH: 61G15-23.002(2) FL. ADMIN. CODE. |
| A COVER SHEET OR INDEX SHEET FOR ENGINEERING |
| SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE |
| SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION & |
| PREPARATION OF EACH SECTION OF THE ENGINEERING |
| SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER |
| SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER |
| THE COVER SHEET OR INDEX SHEET. . |
| |
| PLEASE ALSO NOTE PAGE (1) OF THIS BOOK IS SIGNED AND |
| SEALED THE LAST PARAGRAPH READS: ONCE THE PACKAGE HAS |
| BEEN REVIEWED, WE WILL PROVIDE A FULL PRINTED AND |
| SEALED FINAL PACKAGE. PLEASE PROVIDE. |
| |
| |
| 2) PROVIDE WIND DESIGN CRITERIA 2010 FBC-B 1603.1.4. |
| |
| 3) PLEASE PROVIDE THE STRUCTURAL DESIGN IN COMPLIANCE |
| WITH ASCE 7-10. 1604.1 & 1604.2. |
| |
| 4) NO INFORMATION WAS PROVIDED FOR THE PILING THAT WILL |
| HOLD THE DOCK IN PLACE AND KEEP IT FROM SLIPPING |
| LATERALLY BY EITHER WIND AND OR WATER. 2010 FBC-B |
| 1803.5.5 DEEP FOUNDATIONS. |
| |
| 5) REFERS BACK TO COMMENT # 1. STRUCTURAL PLANS WILL BE |
| REQUIRED TO BE DESIGNED BY A FLORIDA REGISTERED |
| ENGINEER. PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING |
| FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND |
| SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE |
| DOCUMENT. |
| FL ADMIN CODE 61G15-23.002 ENGINEERS |
| EFFECTIVE DATE 05/06/2009 |
| (2)(A) EVERY SHEET OF PLANS AND PRINTS WHICH MUST BE |
| SEALED UNDER THE PROVISIONS OF CHAPTER 471, F.S., SHALL |
| BE SEALED, SIGNED AND DATED BY THE PROFESSIONAL |
| ENGINEER IN RESPONSIBLE CHARGE. |
| |
| |
| 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |